scispace - formally typeset
Search or ask a question
Journal ArticleDOI

A Battery Energy Management Strategy for U.K. Enhanced Frequency Response and Triad Avoidance

22 Mar 2018-IEEE Transactions on Industrial Electronics (IEEE)-Vol. 65, Iss: 12, pp 9509-9517
TL;DR: This paper describes a control algorithm to deliver a charge/discharge power output in response to changes in the grid frequency constrained by the National Grid Electricity Transmission while managing the state of charge of the BESS to optimize the availability of the system.
Abstract: This paper describes a control algorithm for a battery energy storage system (BESS) to deliver a charge/discharge power output in response to changes in the grid frequency constrained by the National Grid Electricity Transmission (NGET)—the primary electricity transmission network operator in the U.K.—while managing the state of charge of the BESS to optimize the availability of the system. Furthermore, this paper investigates using the BESS in order to maximize triad avoidance benefit revenues while layering other services. Simulation using a 2 MW/1 MWh lithium–titanate BESS validated model is carried out to explore possible scenarios using the proposed algorithms. Finally, experimental results of the 2 MW/1 MWh Willenhall Energy Storage System verify the performance of the proposed algorithms.

Summary (1 min read)

Introduction

  • Battery energy storage; enhanced frequency response; frequency stability; grid support; lithium-titanate; triad avoidance; Willenhall energy storage.
  • BESSs using various battery chemistries are installed around the world for grid support [4].
  • Maintaining the grid at a nominal frequency (i.e. 50 Hz for the UK) requires the management of many disparate generation sources against varying loads.
  • In Section III, three different EFR service models are developed to evaluate control strategies for delivering a real-time response to deviations in the grid frequency.
  • Finally, the change in power output per time step (1 second) for each zone is determined using the given ramp-rate limits given in [4].

A. Simulation results of EFR Model-1

  • In order to show the performance of the reported EFR algorithm in Section III, the real grid frequency data for the 21st of October of 2015 [23] is employed herein, as this particular day is known to have a large period of under frequency.
  • Calculated power dictated by EFR specification, also known as *CPower.
  • Because of the SOC reaching 0% and therefore there is no power available for delivery to the grid.
  • This non-conformance would cause a penalty in the SPM and hence it is necessary to improve the EFR control algorithm to minimise such occurrences.

A. Simulation Results of EFR Model-2

  • Model-2 introduces the extended grid frequency event timer and cuts the EFR power output after 15 minutes (Fig. 3).
  • The same frequency data is injected into Model-2 capturing 13 15- minute extended frequency events (Fig. 5(d)).
  • Therefore, the BESS is 100% available for providing power according to the EFR specification.

B. Simulation Results for EFR Model-3

  • The EFR algorithm implemented in Model-3 allows for the charge/discharge of the battery during the 30-minute rest period (Fig. 3).
  • The model is simulated with the 21st October 2015 grid frequency data [23] as shown in Fig.
  • This is a substantial achievement in terms of maximising the utilisation of the BESS stored energy.

C. Results Analysis

  • It was shown that, for the historical dataset considered, the basic EFR algorithm, Model-1, would not be able to manage the extended 15-minute grid frequency events, thus, causing the battery’s SOC to drop to 0%, which would incur a service performance penalty charge.
  • T. Feehally et al., "Battery energy storage systems for the electricity grid: UK research facilities," in IET Int. Conf. Power Electron., Mach.
  • He is a Senior Lecturer in the Department of Electrical and Electronic Engineering, the University of Sheffield, with particular interest for research into energy storage and management, power electronics, and intelligent systems.

Did you find this useful? Give us your feedback

Content maybe subject to copyright    Report

This is a repository copy of A Battery Energy Management Strategy for UK Enhanced
Frequency Response and Triad Avoidance.
White Rose Research Online URL for this paper:
http://eprints.whiterose.ac.uk/129204/
Version: Accepted Version
Article:
Mantar Gundogdu, B., Nejad, S., Gladwin, D.T. orcid.org/0000-0001-7195-5435 et al. (2
more authors) (2018) A Battery Energy Management Strategy for UK Enhanced Frequency
Response and Triad Avoidance. IEEE Transactions on Industrial Electronics, 65 (12). pp.
9509-9517. ISSN 0278-0046
https://doi.org/10.1109/TIE.2018.2818642
© 2018 IEEE. Personal use of this material is permitted. Permission from IEEE must be
obtained for all other users, including reprinting/ republishing this material for advertising or
promotional purposes, creating new collective works for resale or redistribution to servers
or lists, or reuse of any copyrighted components of this work in other works. Reproduced
in accordance with the publisher's self-archiving policy.
eprints@whiterose.ac.uk
https://eprints.whiterose.ac.uk/
Reuse
Items deposited in White Rose Research Online are protected by copyright, with all rights reserved unless
indicated otherwise. They may be downloaded and/or printed for private study, or other acts as permitted by
national copyright laws. The publisher or other rights holders may allow further reproduction and re-use of
the full text version. This is indicated by the licence information on the White Rose Research Online record
for the item.
Takedown
If you consider content in White Rose Research Online to be in breach of UK law, please notify us by
emailing eprints@whiterose.ac.uk including the URL of the record and the reason for the withdrawal request.

IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS
Abstract This paper describes a control algorithm for a
battery energy storage system (BESS) to deliver a
charge/discharge power output in response to changes in
the grid frequency constrained by the National Grid
Electricity Transmission (NGET) the primary electricity
transmission network operator in the UK whilst managing
the state-of-charge (SOC) of the BESS to optimise the
availability of the system. Furthermore, this paper
investigates using the BESS in order to maximise Triad
avoidance benefit revenues whilst layering other services.
Simulation using a 2 MW/1 MWh lithium-titanate BESS
validated model are carried out to explore possible
scenarios using the proposed algorithms. Finally,
experimental results of the 2MW/1MWh Willenhall Energy
Storage System (WESS) verify the performance of the
proposed algorithms.
Index Terms Battery energy storage; enhanced
frequency response; frequency stability; grid support;
lithium-titanate; triad avoidance; Willenhall energy storage.
I. INTRODUCTION
ITH increasing environmental concerns about climate
change and burning fossil fuels, and the requirement for
a more sustainable grid, renewable energy sources (RES) play
an essential role in energy continuity for today’s electricity
supply grid [1],[2]. Increased penetration of uncertain and
intermittent RES on power grids causes many challenges for
grid operators including increased frequency fluctuations,
power quality reduction, reduced reliability and voltage
transients [3]. Energy storage systems (ESSs) are one of the
efficient ways to deal with such issues by decoupling energy
generation from demand. Moreover, ESSs can be used to tackle
the power quality concerns, especially in the UK, by providing
ancillary services such as 15-minute fast frequency response,
frequency regulation, Triad avoidance, load levelling and peak
shaving [4], [5].
There are various types of existing ESSs such as pumped
hydro, hydrogen, fuel cells, cryogenic, compressed air,
flywheel and superconducting magnetic storage [6]. In
comparison to such ESSs, the battery energy storage system
(BESS) has numerous advantages including faster response
time compared to conventional energy generation sources,
energy efficiency, storage size, long cycle life, low self-
discharge rate, high charging/discharging rate capability, and
low maintenance requirements [7], [8]. The cost of batteries has
been decreasing in recent years and therefore there is now
potential for profitable large-scale grid application. BESSs
mostly participate in balancing demand and supply through
frequency response services, voltage support and peak power
lopping [9], [10] BESSs using various battery chemistries are
installed around the world for grid support [4].
In power distribution networks, the frequency changes
continuously due to the imbalance between total generation and
demand; if demand surpasses generation, a decrease in the
frequency will occur and vice versa [4], [11] Maintaining the
grid at a nominal frequency (i.e. 50 Hz for the UK) requires the
management of many disparate generation sources against
varying loads. The National Grid Electricity Transmission
(NGET) the primary electricity transmission network operator
in the UK has introduced a new faster frequency response
service, called Enhanced Frequency Response (EFR), to assist
with maintaining the grid frequency closer to 50 Hz under
normal operation [12]. A BESS is an ideal choice for delivering
such a service to the power system due to its rapid response and
its capability to import/export [4]. In the UK, there are limited
numbers of installed BESS facilities which are suitable for
providing grid support. In 2013, The UK’s first grid-tie lithium-
titanate BESS, the Willenhall Energy Storage System (WESS),
was installed by the University of Sheffield to enable research
on large scale batteries and to create a platform for research into
grid ancillary services [4], [8], [13].
In the UK, the “Triadrefers to the three half-hour settlement
periods with the highest system demand between the months of
November and February, separated by at least ten clear days.
The timing of these peaks is typically one period between
1600hrs to 1800hrs. These three periods are not known in
advance and therefore are determined from the measured data
analysed in March of every year. Half-hourly metered (HHM)
Post Conference Paper
A Battery Energy Management Strategy for
UK Enhanced Frequency Response and
Triad Avoidance
B. Gundogdu, S. Nejad, D. T. Gladwin, M. P. Foster, and D. A. Stone
W
Manuscript received Month xx, 2xxx; revised Month xx, xxxx;
accepted Month x, xxxx.
This work was supported in part by the UK Engineering and
Physical Sciences Research Council under Grant EP/N032888/1.
Authors are with the department of Electronic and Electrical
Engineering at the University of Sheffield, U.K. (emails:
bmantar1@sheffield.ac.uk; shahab.nejad@sheffield.ac.uk;
d.gladwin@sheffield.ac.uk; m.p.foster@sheffield.ac.uk;
d.a.stone@sheffield.ac.uk)

IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS
electricity customers in the UK pay charges proportional to
their consumption during the Triad; this is called the
Transmission Network Use of Service (TNUoS). The HHM
customers can minimise their TNUoS charges by reducing their
demand during Triad periods. Many commercial customers
have an energy storage device or back-up generators to ensure
the maintenance of critical supplies in case of a failure that can
also be engaged to decrease Triad demand; this is known as
‘Triad avoidance’ [14]-[19]. It is also possible for generating
assets such as BESSs to export power to the grid during the
Triad, this results in a payment from the electricity supplier
known as the Triad Avoidance Benefit (TAB). It is a complex
task to predict the Triad periods in advance, however, many
electricity suppliers offer Triad prediction services based on
insufficient system margin (NISM) provided by NG and other
factors such as the weather forecast [16].
Since the EFR is introduced as a new UK grid balancing
service published in the late of 2016, in literature there are only
a few papers about EFR service delivery for grid support. In
[20], a new EFR control algorithm implemented in the DC/AC
converter of a BESS was developed to fulfil the NGET EFR
service requirements, however in this paper EFR control is
achieved with battery energy management system rather than
controlling the energy storage converter. The study [20]
compares the performance of the EFR Sevice-1 (wide
deadband) and Service-2 (narrow dead-band), and it was stated
that the narrow service is technically more challenging, likely
requiring four time the storage capacity of the wide service.
That control algorithm does not cover the 15-mins frequency
event control to be able to increase the availability of the BESS,
especially with the narrow dead-band. However, this paper
extends the basic EFR control algorithm with the two different
extended 15-mins frequency event controls to achieve a
maximum BESS availability for delivering EFR service. In
addition, in [20], the algorithm manages the SOC of the BESS,
maintaining at 49-51%. But, the SOC band should not be kept
at less than 5% SOC band in order to reduce battery degradation
and hence prolong its lifetime.
In [21], Cooke et al. present a method of providing the new
EFR service to avoid the necessity of holding more FFR in
reserve when system inertia falls. That study also introduced
several alternative response curves which indicate that if
arresting the fall in grid frequency in the event of a drop in
generation is an important aspect of the control design, then a
stepped response may provide a better service. An energy
storage strategy based on PI control can help with restoration
and damping of frequency. However, that response time will be
slower than a stepped response so that stability can be ensured.
In [22], the authors investigate the possible performance of a
BESS in EFR provision, by simulating its response to grid
frequency according to the EFR service requirements, and this
evaluating its ability to exchange energy for the service, a
service performance indicator, and the possible aging related to
battery cycling. Different EFR power versus frequency
characteristics, BESS technologies and BESS energy capacities
are considered in [22]. It was also assumed that the BESS are
connected to the UK or to the Continental Europe (CE)
synchronous area; therefore, for the CE system those
requirements are adjusted according to the CE frequency
behaviour. However, a major specification of the EFR service
is to consider ramp-rate limits in the UK requirements, it was
not considered in [22] for simplicity; power exchange rate
limits internal to the batteries was also neglected. In addition,
that study did not cover an extended 15-min frequency event
control in order to increase the batteries availability.
In contrast to other recent works in the field; the main
contribution of this paper is to present a novel control algorithm
that enables BESSs to provide a bi-directional power in
response to changes in the grid frequency, whilst managing the
SOC of the BESS to optimise availability of the system.
Moreover, this study introduces a strategy to generate
additional revenues from ancillary services such as Triad
Avoidance only available during the winter season.
Moreover, this paper considers layering the new UK grid
frequency balancing service, EFR, with Triad Avoidance in
order to maximise the system’s availability and profitability. It
should be noted that the previous basic study [4] presented
initial three EFR control methodologies with their simulation
results; and this paper extends to show how this can be used to
maximise profits from other services such as Triad Avoidance.
This paper also includes experimental validation with a
2MW/1MWh lithium-titanate BESS, commissioned and
operated by the University of Sheffield, which is the largest
research only platform for grid-tie energy storage applications.
This paper is organised as follows. In Section II, the technical
specification of the new UK EFR service is described. In
Section III, three different EFR service models are developed
to evaluate control strategies for delivering a real-time response
to deviations in the grid frequency. The first model introduces
a control algorithm designed to meet the technical requirements
of NGET specifications [12]. The second model addresses the
EFR service design with an extended 15-minute frequency
event control, in order to optimise the use of the available stored
energy. The third model extends the EFR control algorithm to
include a dynamic SOC target to maximise the energy stored on
predicted Triad days. In Section IV the simulation results based
on the 2 MW / 1 MWh BESS are analysed to verify the transient
performance of the proposed control strategy. In Section V, the
performance of the EFR service delivery through TAB is
quantified and the performance of the proposed EFR control
algorithm is verified experimentally with the 2MW / 1MWh
WESS in Section VI.
II. EFR SERVICE TECHNICAL SPECIFICATIONS
EFR is introduced as a new fast frequency response service
for grid balancing that can deliver full-scale active power within
one second of registering a grid frequency deviation. NGET
prepared an EFR specification to facilitate a tender competition
for 200 MW of support provision to be distributed amongst
potential energy storage providers in 2016 [12], which is
described as follows.

IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS
Fig. 1. NGET specifications (a) EFR envelope and (b) power zones [12].
TABLE I
EFR ENVELOPE FREQUENCY AND POWER BOUNDARIES [12]
Power (%)
Ref.
Point
Service-1
Service-2
Ref.
Point
Service-1
Service-2
A
B
C
D
E
F
49.5
49.75
49.95
50.05
50.25
50.5
49.5
49.75
49.985
50.015
50.25
50.5
t
u
v
w
x
y
z
100
44.44444
9
0
-9
-44.44444
-100
100
48.4536
9
0
-9
-48.4536
-100
Energy storage providers must respond to deviations in
nominal frequency (50 Hz) by decreasing or increasing their
power output. Specifically, energy storage devices must
provide power to the grid to respond to deviations in frequency
outside of a dead band (DB). Providers must deliver continuous
power to the grid as described in one of the two EFR service
envelopes (Service-1, Service-2) of Table I [12]. As seen in
Error! Reference source not found.(a), the power level must
remain within the upper and lower envelopes at all times; power
provided outside the envelope will decrease the service
performance measurement (SPM), and thus reduce the income
revenue [12]. In DB, the reference power profile is at zero MW
output and hence providers do not have to respond to changes
in the grid frequency. The BESS can be freely operated to
charge/discharge in DB, however, the maximum export/import
power must not exceed 9% of the BESS’s full-scale range [12].
Providers may operate anywhere within the upper and lower
envelopes to deliver a continuous service to the power system,
with respect to the specified limitations on ramp rates as given
in [4],[12]. For a BESS, this effectively provides some control
over state-of-charge (SOC) of the battery. For the zones A, C, D
in Error! Reference source not found.(b), the ramp rate must
obey the specified values in [4], [12]. Operation in zones C and
D will result in payments at a lower SPM. Hence, in such cases,
EFR power output has to return to the specified envelope with
respect to the ramp-rate limits given in [4]. Ramp-rate zone B is
described as being the area between the upper and lower
envelopes, excluding the DB, and extends to achieve the full
power capability at ±0.5 Hz [12]. The allowable ramp rates
within zone B depend on the rate of change of frequency. For
EFR Service-1 and Service-2, the ramp rate limitations for all
frequencies in zone B are shown in [4]. With these ramp limits,
output power changes proportionally to changes in grid
frequency, whilst allowing the energy storage providers some
flexibility [12] to manage the battery SOC.
III. EFR DESIGN ALGORITHM
A BESS model is developed in MATLAB/Simulink and
verified against experimental operation of the WESS. An EFR
control algorithm is then implemented on the model to deliver
a grid frequency response service to the NGET specification.
Fig. 2 presents the EFR control scheme implemented in EFR
Model-1 [4], where the inputs are real-time grid frequency ()
and battery SOC, and the output is the required EFR power.
Fig. 2. EFR control scheme implemented in EFR Model-1 [4].
The algorithm starts by detecting the position of the
measured grid frequency with respect to the zones bounded by
vertical lines A’ to ‘F’ in Fig. 1 (a). This is achieved by the
‘EFR Power Calculation’ block (labelled ‘1’), where the
required EFR response envelopes are calculated. In the 2 MW
BESS model, the frequency and power bounds are calculated as
a function of the limits denoted in Fig. 1 (a), with their values
declared in Table I. The power output is restricted to ±180 kW
(i.e. 9% of 2 MW) within the DB and both services include an
upper, base line and lower power line denoted, and ,
respectively. Block 2 selects the required power line with the
decision being based on the measured SOC. For example, if the
current SOC is below the desired SOC range, the demanded
power is calculated using the equations derived for the upper
line (). This has the effect of either importing energy to charge
the battery or minimising the exported energy to maintain a
desired SOC range. ‘Zone Assignment’ (Block 3) is responsible
for identifying the current operating zone (refer to Fig. 1(b)) for
the calculation of the power-output levels.
t
u
v
w
x
y
z
A
B
C
D
E
F
Upper
limit
Lower
limit
Base line
Output power
Frequency
DB
(a)
(b)
EFR Power
Calculation
f (Hz)
U, Z, L
Ramp-
Rate
Limiter
SOC
Power Setpoint
- +
Measured
Power
Zone
df / dt
f (Hz)
f (Hz)
SOC
error
State
Power
Output
State
Assignment
&
EFR Power
Set Point
Zone
Assignment
1
2
3
4

IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS
Finally, the change in power output per time step (1 second)
for each zone is determined using the given ramp-rate limits
given in [4]. In this study, battery SOC is calculated using (1)
[4], where SOC

, and

represent initial SOC, Watt-hour
capacity and instantaneous battery power, respectively.
SOC
out
SOC
init
batt


(1)
Fig. 3. Flow chart showing the structure of the two proposed battery energy
management strategies for enhanced frequency response in the UK [4].
The EFR specification defines frequency outside DB for
longer than 15 minutes as an extended event, whereby after the
15 minutes, it is optional to deliver power for up to 30 minutes
post the grid frequency returning to DB. In order to increase the
availability of the BESS in Model-1, by avoiding SOC limits,
an extended 15-minute frequency event control algorithm is
implemented in EFR Model-2 and Model-3, as given in Fig. 3.
EFR Model-2 introduces a timed control block, which measures
the length of time that the grid frequency is continuously
outside of the DB. If this block measures a value higher than 15
minutes, then the BESS’s output power is set to zero. The BESS
remains in this state until the system frequency returns within
DB, at which point a second timer starts timing for 30 minutes
and the output power stays at zero until the timer expires, at
which point, the EFR control is reset back to operating as EFR
Model-1. EFR Model-3 allows the BESS to manage its SOC
between its upper (SOC

) and lower limits (SOC

) during the
30-minute rest period by charging and discharging the battery
within the ±9% power limits.
IV. SIMULATION RESULTS OF EFR MODELS
Using a real-time frequency data set obtained from NGET
[23], the three EFR models are simulated in
MATLAB/Simulink. The simulation results presented in this
paper are all based on a 1 MWh BESS model, which has been
experimentally validated on the WESS plant in the UK, with a
maximum EFR power of ±2 MW. Table V shows the
parameters used in the EFR models.
A. Simulation results of EFR Model-1
In order to show the performance of the reported EFR algorithm
in Section III, the real grid frequency data for the 21
st
of October
of 2015 [23] is employed herein, as this particular day is known
to have a large period of under frequency.
TABLE I
SYSTEM PARAMETERS [12]
Parameter
Value
Nominal frequency
Low/high DB
Max/min EFR power limit
Battery rated power/capacity
Battery initial SOC (SOC

)
SOC band (SOC

- SOC

)
Inverter efficiency (

)
Battery charge/discharge efficiency (
/
)
50 Hz
±0.015 Hz (Service-2)
±2 MW
2 MW/1 MWh
50%
45-55%
97%
94%
Fig. 4 shows the simulation results of Model-1 for a ‘Service-
2’ EFR with a target SOC band of 45-55%. On the frequency
plot, the DB (±0.015 Hz) is shown by the green lines. It is clear
that the SOC sharply drops, reaching 0% at 11:00, and stays
there for ~30mins due to the grid frequency demands at that
time. As the frequency stabilises, the EFR algorithm charges
the battery when it is permissible (frequency in DB) and returns
the SOC to within the specified band of 45-55%. The power
response versus frequency plot of EFR Model-1 for 21
st
October 2015 is shown in Fig. 7(a). The red lines represent the
upper, reference and lower EFR power lines. It can be seen that
the EFR power (blue circles) does not remain within the
required zones of ‘A’ and ‘B’. As outlined in Fig. 1, this is
*CPower: Calculated
power dictated by
EFR specification.
Start
Measure frequency
Frequency in
DB?
PowerOut = CPower
Event Counter=0
Timer1=0
Timer2=0
End
Yes
No
Start/Continue Timer1
Timer1≥15 mins
No
PowerOut = CPower
Yes
M2/M3
M2
Start/Continue Timer2
Timer2≥30 mins
PowerOut=0
No
Yes
PowerOut = CPower
End
Model 2
Event Counter=1
Stop Timer1 & Timer2
M3
Start/Continue Timer2
Timer2≥30 mins
PowerOut = CPower
Yes
End
No
Frequency in
DB?
Yes
SOC<SOClow?
No
SOC>SOCup?
Yes
Yes
No
PowerOut=0
PowerOut = CPower
(charging battery)
PowerOut=0
No
Model 3
PowerOut = CPower
(discharging battery)
Event Counter=1
Stop Timer1 & Timer2

Citations
More filters
Journal ArticleDOI
TL;DR: Simulation result show that the proposed algorithm delivers both dynamic and non - dynamic firm frequency response (FFR) and also enhanced frequency response (EFR) to NGET specifications while generating arbitrage revenue as well as service availability payment s in the balancing market.
Abstract: Battery energy storage systems (BESS) are widely used to smooth power fluctuations and maintain the voltage and frequency of the power feeder at a desired level. T he National Grid Electricity Transmission (NGET), the primary electricity transmission network operator in the UK, has introduced various frequency response servic es that are designed to provide a real - time response to deviations in the grid frequency. In this study , a control algorithm is developed which generates a charge/discharge power output with respect to deviations in the grid frequency and the requisite service specifications. Using historical UK electricity prices, a new balancing service scheduling approach has also been developed to maximize energy arbitrage revenue by layering different types of balancing services throughout the day . Simulation result s show that the proposed algorithm delivers both dynamic and non - dynamic firm frequency response (FFR) and also enhanced frequency response (EFR) to NGET specifications while generating arbitrage revenue as well as service availability payment s in the balancing market. A comparative study is also presented to compare the yearly arbitrage revenue obtained from the work presented in this paper and a previous reference study . Finall y, exper imental results of a grid - tied 2MW /1MWh BESS have been used for verification purposes.

15 citations

Journal ArticleDOI
03 Mar 2021-Energies
TL;DR: It has been demonstrated that a droop-controlled BESS can greatly improve frequency response, producing both faster reaction and smaller frequency deviation in a power system with high renewable energy penetrations.
Abstract: In power systems, high renewable energy penetration generally results in conventional synchronous generators being displaced. Hence, the power system inertia reduces, thus causing a larger frequency deviation when an imbalance between load and generation occurs, and thus potential system instability. The problem associated with this increase in the system’s dynamic response can be addressed by various means, for example, flywheels, supercapacitors, and battery energy storage systems (BESSs). This paper investigates the application of BESSs for primary frequency control in power systems with very high penetration of renewable energy, and consequently, low levels of synchronous generation. By re-creating a major Australian power system separation event and then subsequently simulating the event under low inertia conditions but with BESSs providing frequency support, it has been demonstrated that a droop-controlled BESS can greatly improve frequency response, producing both faster reaction and smaller frequency deviation. Furthermore, it is shown via detailed investigation how factors such as available battery capacity and droop coefficient impact the system frequency response characteristics, providing guidance on how best to mitigate the impact of future synchronous generator retirements. It is intended that this analysis could be beneficial in determining the optimal BESS capacity and droop value to manage the potential frequency stability risks for a future power system with high renewable energy penetrations.

13 citations

Journal ArticleDOI
TL;DR: A method was proposed to estimate the EFR capacity of a population of industrial heating loads, bitumen tanks, and a decentralized control scheme was devised to enable them to deliver EFR, and results showed that bitumen Tanks delivered high-quality service but underperformed for service-2-type EFR with much narrower deadband.
Abstract: Increasing penetration of renewable generation results in lower inertia of electric power systems. To maintain the system frequency, system operators have been designing innovative frequency response products. Enhanced frequency response (EFR) newly introduced in the UK is an example with higher technical requirements and customized specifications for assets with energy storage capability. In this paper, a method was proposed to estimate the EFR capacity of a population of industrial heating loads, bitumen tanks, and a decentralized control scheme was devised to enable them to deliver EFR. Case study was conducted using real UK frequency data and practical tank parameters. Results showed that bitumen tanks delivered high-quality service when providing service-1-type EFR, but underperformed for service-2-type EFR with much narrower deadband. Bitumen tanks performed well in both high- and low-frequency scenarios, and had better performance with significantly larger numbers of tanks or in months with higher power system inertia.

12 citations

Journal ArticleDOI
08 Sep 2020-Energies
TL;DR: A control that maintains SOC at a certain level is introduced that focuses on the battery operation function, which is determined from five control scenarios, and the results correspond to the predetermined criteria control.
Abstract: The dependence of distributed generations (DGs) on climate conditions and fluctuating load demands are the challenges for the implementation of battery energy storage systems (BESSs) in islanded microgrids. BESS participation in system frequency regulation becomes one of the solutions to those challenges. Frequency regulation by BESS can be realized by applying the load-frequency control (LFC) in BESS. However, this participation clearly poses problems for the battery state of charge (SOC), as the battery is often overcharged or undercharged. In this paper, a control that maintains SOC at a certain level is introduced. This control strategy focuses on the battery operation function, which is determined from five control scenarios. All scenarios are achieved by applying the droop reference shifting method in the LFC to allow battery operation change. Control verification is carried out on an islanded microgrid system that experiences load demand changes and photovoltaic (PV) output power changes. The test results show that the SOC is maintained at 45–75% by applying load and PV power variations. The results correspond to the predetermined criteria control.

11 citations

Journal ArticleDOI
09 Mar 2021
TL;DR: In this article, a lifetime analysis of battery energy storage systems (BESSs) providing PFR considering IGBT modules, electrolytic capacitors and electrochemical storage degradation is presented, evaluating the benefits of deploying PE-based BESS in the European grid.
Abstract: Battery Energy Storage Systems (BESSs) are a new asset for Primary Frequency Regulation (PFR), an ancillary service for improving the grid stability. The system operators determine the implementation and remuneration of PFR. However, assessing the revenue stream is not enough to define the business case, as also the components’ lifetime has to be estimated. Previous studies of lifetime estimation for BESSs performing PFR considered only the electrochemical storage, disregarding the power electronics (PE). Nonetheless, researchers have shown the importance of estimating PE wear due to the operation when applied in renewable energy generation and microgrids. This paper presents a lifetime analysis of BESSs providing PFR considering IGBT modules, electrolytic capacitors and electrochemical storage degradation. The lifetime information is used to estimate BESS's Net-Present-Value (NPV), evaluating the benefits of deploying PE-based BESS in the European grid. A comparison between different countries, Germany, the Netherlands, and the U.K., is performed, considering the PFR implementation and remuneration differences. The analysis shows that the BESS management strategy can extend its lifetime and that the component that exhibits the shortest lifetime is the electrochemical storage. The PE components are subject to low wear due to the low power utilization and, therefore, small thermal swings while performing PFR. In conclusion, the provision of PFR by means of BESS has been found to be profitable in all three countries. However, in the Netherlands, the potential NPV has been estimated to be 47% and 76% higher than in Germany and the U.K., respectively.

11 citations

References
More filters
Journal ArticleDOI
TL;DR: In this paper, the authors discuss the present status of battery energy storage technology and methods of assessing their economic viability and impact on power system operation and suggest a likely future outlook for the battery technologies and the electric hybrid vehicles in the context of power system applications.

1,627 citations


"A Battery Energy Management Strateg..." refers background in this paper

  • ...dro, hydrogen, fuel cells, cryogenic, compressed air, flywheel, and superconducting magnetic storage [6]....

    [...]

Journal ArticleDOI
TL;DR: In this article, the integration of Li-ion battery into an EV battery pack is investigated from different aspects, namely different battery chemistry, cell packaging, electric connection and control, thermal management, assembly and service and maintenance.

287 citations

Journal ArticleDOI
TL;DR: Novel statistical techniques have been devised to quantify the design and operational requirements of ESS providing frequency regulation services, demonstrated via an illustrative service design and high-resolution frequency data from the Great Britain transmission system.

209 citations


"A Battery Energy Management Strateg..." refers background or methods or result in this paper

  • ...In [20], a new EFR control algorithm implemented in the dc–ac converter of a BESS was developed to fulfill the NGET EFR service requirements; however, in this paper, EFR control is achieved with the battery energy management system rather than controlling the energy storage converter....

    [...]

  • ...In addition, in [20], the algorithm manages the state-of-charge (SOC) of the BESS, maintaining at 49–51%....

    [...]

  • ...The study [20] compares the performance of the EFR Sevice 1 (wide deadband) and Service 2 (narrow deadband), and it was stated that the narrow service is technically more challenging, likely requiring four times the storage capacity of the wide service....

    [...]

Journal ArticleDOI
TL;DR: In this paper, a stochastic unit commitment approach with wind power forecast uncertainty and energy storage is proposed to evaluate the potential value of energy storage in power systems with renewable generation.
Abstract: The fast growing expansion of renewable energy increases the complexities in balancing generation and demand in the power system. The energy-shifting and fast-ramping capability of energy storage has led to increasing interests in batteries to facilitate the integration of renewable resources. In this paper, we present a two-step framework to evaluate the potential value of energy storage in power systems with renewable generation. First, we formulate a stochastic unit commitment approach with wind power forecast uncertainty and energy storage. Second, the solution from the stochastic unit commitment is used to derive a flexible schedule for energy storage in economic dispatch where the look-ahead horizon is limited. Analysis is conducted on the IEEE 24-bus system to demonstrate the benefits of battery storage in systems with renewable resources and the effectiveness of the proposed battery operation strategy.

140 citations


"A Battery Energy Management Strateg..." refers background in this paper

  • ...W ITH increasing environmental concerns about climate change and burning fossil fuels, and the requirement for a more sustainable grid, renewable energy sources (RES) play an essential role in energy continuity for today’s electricity supply grid [1], [2]....

    [...]

Journal ArticleDOI
TL;DR: This paper addresses the sizing issue of an aggregated BESS by a series of system level performance tests with different BESS penetration rates and response effectiveness of the BESS with different levels of disturbances is analyzed.
Abstract: With the increased environmental concern, the photovoltaic (PV) generation capacity is growing in today’s power systems. As the PV penetration rate increases, the intermittency and uncertainty of PV systems will cause frequency regulation issues. When rapid fluctuations take place, the system requires fast responding regulation to recover the frequency within a short period of time. Traditional power plants with slow dynamics are less capable of tracking the fast-changing regulation signal. In this context, a battery energy storage system (BESS) is considered as an effective regulation source to respond immediately to frequency deviations. This paper addresses the sizing issue of an aggregated BESS by a series of system level performance tests with different BESS penetration rates. The evaluation criteria are the control performance standards 1 and 2. Response effectiveness of the BESS with different levels of disturbances is also analyzed, with comparison to that of the traditional power plants. The proposed BESS aggregation controller is also validated using software simulations and a hardware testbed.

134 citations


Additional excerpts

  • ...BESSs mostly participate in balancing demand and supply through frequency response services, voltage support, and peak power lopping [9], [10] BESSs using various battery chemistries are installed around the world for grid support [4]....

    [...]

Frequently Asked Questions (1)
Q1. What are the contributions in this paper?

This paper describes a control algorithm for a battery energy storage system ( BESS ) to deliver a charge/discharge power output in response to changes in the grid frequency constrained by the National Grid Electricity Transmission ( NGET ) – the primary electricity transmission network operator in the UK – whilst managing the state-of-charge ( SOC ) of the BESS to optimise the availability of the system. Furthermore, this paper investigates using the BESS in order to maximise Triad avoidance benefit revenues whilst layering other services.