An Improved Droop Control Method for DC Microgrids Based on Low Bandwidth Communication With DC Bus Voltage Restoration and Enhanced Current Sharing Accuracy
Summary (2 min read)
Introduction
- The conventional dc droop control method is realized by linearly reducing the dc output voltage as the output current increases.
- The local controller of each converter individually adjusts each output current, so the current sharing accuracy is significantly improved.
- Section III introduces the principle of the proposed control scheme.
II. LIMITATIONS OF THE CONVENTIONAL DROOP CONTROL
- The conventional droop control method in a dc microgrid is achieved by linearly reducing the voltage reference when the output current increases.
- The first limitation of the conventional droop control method is the degradation of the current sharing accuracy.
- Since the output voltage cannot be exactly the same due to the additional voltage drop across the line resistances, the load current sharing accuracy is lowered down.
- Second, the voltage deviation exists due to the droop action.
- The above two limitations of the conventional droop control method are analyzed in detail as follows.
A. Current Sharing Accuracy Degradation
- This controller can be implemented by means of a virtual resistance; this method is also named adaptive voltage positioning [29].
- If the line resistance is taken into account, as in the reactive power sharing in ac microgrids with inductive line impedances, the dc output voltages for the local converters are not exactly the same.
- Therefore, a larger virtual resistance Rdi can be selected.
- (5) However, the above assumption is only suitable for a small system.
- This is the first limitation of the conventional droop control method.
B. DC Voltage Deviation
- The analysis is also shown in Fig. 3. When the interfacing converter operates in the open-circuit condition, the dc voltage deviation is zero.
- When the dc output current is not equal to zero, the dc voltage deviation exists and its value varies with the load current.
- To guarantee that the voltage deviation does not exceed its maximum acceptable value, the value of the droop coefficient Rdi should be limited: dcmax di dcfli v R i (7) where idcfli is the full-load output current of converter #i.
- The deviation of the output voltage is the second limitation of the conventional droop control method.
III. PRINCIPLE OF THE PROPOSED CONTROL METHOD
- In order to solve the problems imposed by the two limitations of the conventional droop control method, an improved droop control method based on LBC is proposed.
- Here, the conventional droop control method is used to achieve proportional load current sharing approximately.
- Then, the output voltages and currents in the dc sides of the converters are transferred to the other converters using the LBC network.
- Therefore, the proportional output current sharing is guaranteed.
- Hence, during the same length of time period, the amount of data on the communication network for the LBC-based method is highly reduced to 1/N in contrast with the HBC-based method.
IV. STABILITY ANALYSIS OF THE PROPOSED CONTROL SYSTEM
- (10) The detailed model of the control diagram for analyzing the system stability is shown in Fig.
- The closed-loop dominant poles of (21) for different communication delays are shown in Fig.
- The value of Rline1 is fixed, while the value of Rline2 changes to test the stability of the control system for different conditions.
- Fig. 8 shows that the value of the line resistance affects two dominant poles.
- If the values of the line resistances and the current sharing proportion do not meet the relationship in (26), the dc output voltage in each converter cannot be the same.
V. SIMULATION TEST
- Simulation test based on Matlab/Simulink is performed to demonstrate the feasibility of the proposed method.
- It is seen that when the proposed method is activated, the dc voltage of each converter is restored and the current sharing accuracy is enhanced.
- Meanwhile, different power load are used to test the performance of the proposed control system.
- Meanwhile, the transient response with the step-up of the load power is shown in Fig. 16.
- It is also found that the proposed approach is still valid for the power load-step.
VI. EXPERIMENTAL VALIDATION
- A 2×2.2 kW prototype with two parallel converters is implemented to validate the proposed control system.
- When the communication delay is set to 20 ms, the overshoot and oscillation of the dc output waveforms are more severe than when the communication delay is set to 1 μs; however, these waveform characteristics are still acceptable.
- To further test the applicability of the control system, different line resistances are tested.
- The corresponding output voltage and current waveforms are shown in Fig. 21 and Fig. 22.
- The transient responses of equal load current sharing are shown in Fig. 17, and the output voltage and current waveforms when idc1/idc2 = 0.5 are shown in Fig. 23.
VII. CONCLUSION
- Concretely, average voltage and average current PI controllers are employed to enhance the load current sharing accuracy and restore the local dc output voltage.
- Hence, the distributed control system that meets the decentralized configuration of microgrid is realized.
- It is demonstrated that even though a high communication delay is employed (approximately 20 ms), the stability of the control system can also be guaranteed.
- It is demonstrated that with the integral controller, the current sharing accuracy can be exactly reached.
- Meanwhile, the average value of the output voltage can be restored and each voltage is guaranteed to be within the acceptable range.
Did you find this useful? Give us your feedback
Citations
1,131 citations
Cites background or methods from "An Improved Droop Control Method fo..."
...While stability is thoroughly discussed in Section V, more details on current sharing accuracy problem can be found in [23] and [53] and references therein....
[...]
...In [53], two additional PI controllers are employed to control the average dc voltage and average dc current obtained by the low-bandwidth communication-based consensus algorithm....
[...]
...In comparison to [53], the methods proposed in [22] and [80] require only the neighbors’ information, and the control diagram is implemented on a sparse communication graph across the MG, reducing the number of communication lines....
[...]
964 citations
Cites background from "An Improved Droop Control Method fo..."
...This topology, operated at low voltage, has by now been the most widely studied in the literature [15], [18], [46], [48]–[50], [55], [98]–[103]....
[...]
715 citations
Cites background from "An Improved Droop Control Method fo..."
...The line impedance effect is taken into account in [43], with a fully connected communication network....
[...]
...The voltage regulation requirement is redefined to incorporate the line impedance effect in [43] and [53]....
[...]
...Despite simplicity and ease of implementation, the conventional droop method suffers from poor voltage regulation and load sharing, particularly when the line impedances are not negligible [43]–[46]....
[...]
707 citations
Cites background from "An Improved Droop Control Method fo..."
...some cases, low-bandwidths communication systems are used in droop control strategies [123], [124] to improve the droop control performance....
[...]
598 citations
References
4,145 citations
"An Improved Droop Control Method fo..." refers background or methods in this paper
...Power line communication (PLC) or LBC is commonly utilized [22], [28]....
[...]
...put current increases [22]....
[...]
...To satisfy the requirements of a distributed configuration, droop control without communication or with LBC is commonly accepted as an efficient power sharing method in a microgrid [22]....
[...]
...To solve this problem, a centralized secondary controller was proposed to eliminate the voltage deviation [22]; however, the influence of the line resistance was not taken into account....
[...]
3,799 citations
"An Improved Droop Control Method fo..." refers background in this paper
...The power electronics interfacing converter control is a key issue in the operation of a microgrid [16], [17], particularly for the load power sharing between different modules [18], [19]....
[...]
2,482 citations
"An Improved Droop Control Method fo..." refers background in this paper
...on this topic is mostly focusing on ac microgrids, since the utility electrical grid relies on ac systems [2-6]....
[...]
2,296 citations
"An Improved Droop Control Method fo..." refers background in this paper
...The power electronics interfacing converter control is a key issue in the operation of a microgrid [16], [17], particularly for the load power sharing between different modules [18], [19]....
[...]
2,076 citations