Dielectric Losses and Stresses in Relation to Cable Failures

D. W. Roper
- 01 Jan 1922 - 
- Vol. 41, Iss: 6, pp 547-557
Reads0
Chats0
TLDR
In this article, the authors present a temperature survey of the 20-kv. cable and show that nearly all of the burnout occurred in a portion of the conduit near the substation, which conduit contained a large number of heavily loaded cables, and in which the temperature was 10 deg. to 15 deg. cent. higher than the rest of the line.
Abstract
When transmission cables were first operated at potentials exceeding about 7500 volts, it was noted that cable failures occurred in service with loads materially below those which had theretofore been found to be permissible with low-voltage cables, and this reduction in carrying capacity increased with increase of the normal working potential. For example the author has previously reported that No. 0 A. W. G. four conductor cables operating on a four-wire three-phase system with a maximum normal potential of about 4000 volts between phases carry 200 amperes on each of three conductors without damage due to the overheating, whereas a 250,000-cir. mil cable operated at 20,000 volts was found to have excessive burn-outs if the load exceeded 175 amperes per conductor. For a number of years it has been recognized that this reduction in carrying capacity of high-voltage cables was due to the dielectric losses and a number of papers have been presented to the Institute on this subject. A temperature survey of the 20-kv. cable above mentioned showed that nearly all of the burn-outs occurred in a portion of the conduit near the substation, which conduit contained a large nuumber of heavily loaded cables, and in which the temperature was 10 deg. to 15 deg. cent. higher than the rest of the conduit. This portion of the 20-ky. line was replaced over two years ago with cable having a low dielectric loss, since which time no further cable failures have occurred.

read more

Citations
More filters
Journal ArticleDOI

The Klydonograph and Its Application to Surge Investigation

TL;DR: The first experimental model of the klydonograph was described in this article, which used a stationary glass photographic plate in removable plateholders with a moving electrode for connection to a three-phase line.
Journal ArticleDOI

Tests of Paper-Insulated High-Tension Cable

TL;DR: In this article, the purpose and importance of various standard tests of cable, insulation resistance test, highvoltage test, dielectric loss and power-factor test, ionization test, bending test, accelerated life test, preparation of samples for high-voltage tests and tests of components.
Journal ArticleDOI

Accelerated aging tests on high voltage cables and their correlation with service records

TL;DR: In this article, a series of tests was undertaken with the object of developing in a short time the deterioration which had been found in the several cables in service, and a careful comparison of test and service records of the four makes of cable installed in 1926 showed that the cable had a wide range in quality.
Journal ArticleDOI

The Quality Rating of High-Tension Cable With Impregnated-Paper Insulation

TL;DR: In this paper, the authors present a series of laboratory tests to determine what high-voltage tests cable known to be of good quality will withstand as well as the similar tests on other grades of cable.