scispace - formally typeset
Proceedings ArticleDOI

Partial discharge behaviour in oil-impregnated insulation

Reads0
Chats0
TLDR
In this paper, an experimental investigation of partial discharge behavior in a laboratory model of transformer oil-impregnated insulation at high temperature and with different levels of moisture contamination of both the oil and paper was performed.
Abstract
The insulation within an oil-insulated power transformer consists of mainly organic materials including mineral oil, cellulose paper and pressboard layers. The presence of moisture, coupled with high operating temperature in the insulation reduces the dielectric strength of the cellulose paper, the pressboard and the transformer oil. This paper reports results of an experimental investigation of partial discharge behaviour in a laboratory model of transformer oil-impregnated insulation at high temperature and with different levels of moisture contamination of both the oil and paper. The experiments were performed in the laboratory with an environment and configuration similar to practical operating conditions in a transformer. The partial discharge patterns together with inception and extinction data were recorded and correlated with moisture and temperature effects and age of insulation. The thermal generation of gas bubbles and, moisture levels and their associated discharge characteristics were also recorded and analysed. The effect of aged and new transformer oil on partial discharge activity patterns was also investigated.

read more

Citations
More filters
Journal ArticleDOI

Effect of superimposed impulses on AC partial discharge characteristics of oil-impregnated paper

TL;DR: In this paper, the effect of HV impulses on surface and cavity partial discharges (PD) of oil-impregnated paper (OIP) was investigated by subjecting specimens to impulse voltages superimposed on a continuous AC voltage.
Proceedings ArticleDOI

Comparison of partial discharge activity in mineral oil and bio-degradable oil

TL;DR: In this article, the partial discharge activity and characteristics in mineral oil and bio-degradable oil were investigated and the phase resolved distribution was analyzed in terms of phase resolution distribution.

Dielectric Response and Partial Discharge Diagnostics of Insulation Systems by Utilizing High Voltage Impulses

Roya Nikjoo
TL;DR: In this article, power system transients are considered as an opportunity for development of on-line diagnostics of power components and specifically the insulation systems of power transformers and transformers.

Effect of HV Impulses on Partial Discharge Activity in Oil- Impregnated Paper Insulation

TL;DR: In this article, high voltage transients in electrical power systems are mainly caused by lightning strikes and switching operations, and the high voltage transient from its point of origin can propagate in eithe...

Um Estudo Qualitativo das Técnicas Utilizadas para Medição e Localização de Descargas Parciais em Transformadores de Potência

Abstract: Este artigo tem como foco principal apresentar técnicas de medição e localização de Descargas Parciais, doravante DPs, em transformadores de potência. Este procedimento tem como objetivo detectar possíveis falhas no sistema de isolação, tanto em equipamentos novos quanto em equipamento em operação. Atualmente a NBR 6940 regulamenta os procedimentos de ensaio e os níveis admissíveis de DPs. Vários métodos são utilizados para detecção, sendo o mais utilizado o método elétrico. No entanto, tal abordagem pode sofrer influência de interferência eletromagnética quando aplicado a equipamento em operação. Neste contexto, os métodos não elétricos são utilizados na tentativa de identificar e localizar tais distúrbios de modo minimizar a possibilidade de interrupções e prejuízos. Palavras-chave: Descargas parciais. Transformador. Ensaio elétrico. ABSTRACT:
References
More filters
Journal ArticleDOI

Classification of partial discharges

TL;DR: For a long time, classification of partial discharges was performed by eye, by studying discharge patterns at the ellipse of an oscilloscope screen as discussed by the authors, and the introduction of digital processing techniques allowed automation of the recognition procedure.
Related Papers (5)