scispace - formally typeset
Journal ArticleDOI

The load shedding scheme design for an integrated steelmaking cogeneration facility

C.T. Hsu, +2 more
- Vol. 33, Iss: 3, pp 113
Reads0
Chats0
TLDR
In this paper, the coordination of a load-shedding scheme for a large industrial customer with several cogenerator units was developed. But the main focus was on the generator protection scheme.
Abstract
This paper develops the coordination of a load-shedding scheme for a large industrial customer with several cogenerator units. A detailed description of each design procedure is included. The loads are tripped by the underfrequency relays, to prevent the power system from collapse when the plant becomes isolated, due to a utility service outage. Different system fault cases have been selected to derive the proper formulation of a load-shedding scheme, according to the historical operation records. The key factors, such as frequency settings, number of load-shedding steps, size and location of the loads to be tripped, relay time delay, and the coordination with the generator protection scheme, were examined through the simulation of the transient stability program. The proper load-shedding scheme has been designed, and the related hardware has been installed in the plant, to keep the system from blackout when the disturbance occurs.

read more

Citations
More filters
Journal ArticleDOI

Short-term operation planning on cogeneration systems : A survey

TL;DR: In this paper, a survey of the developed researches from 1983 up to 2006 related to the cogeneration systems is presented, focused on short-term operation planning and papers are grouped according to the most important characteristics.
Proceedings ArticleDOI

Optimal load shedding strategy in power systems with distributed generation

TL;DR: An optimal load shedding strategy for power systems with multiple distributed generation is presented and the dynamic and static models of each type following a major disturbance are developed.
Journal ArticleDOI

Transient stability study of the large synchronous motors starting and operating for the isolated integrated steel-making facility

TL;DR: In this paper, the influence of the large motor starting and the large rolling mill operation on the isolated integrated steel cogeneration facility by executing the transient stability analysis was investigated in detail.
Journal ArticleDOI

Modeling and multi-objective optimization of a complex CHP process

TL;DR: Artificial Neural Networks and Adaptive Neuro-Fuzzy Inference Systems are used to generate predictive models of the CHP plant and a slurry drying process to optimize the plant performance in order to maximize the effective electrical efficiency.
Proceedings ArticleDOI

Artificial Neural Network Based Adaptive Load Shedding for an Industrial Cogeneration Facility

TL;DR: To demonstrate the effectiveness of the ANN minimum load-shedding scheme, the traditional method and the present load shedding schemes of the selected cogeneration system are applied for comparison and verification of the proposed methodology.
References
More filters
Journal Article

Load representation for dynamic performance analysis

TL;DR: In this paper, the authors summarized the state of the art of representation of power system loads for dynamic performance analysis purposes, including definition of terminology, discussion of the importance of load modeling, important considerations for different types of loads and different kinds of analyses Typical load model data and methods for acquiring data are reviewed.
Journal ArticleDOI

Computer representation of excitation systems

TL;DR: This paper suggests a common nomenclature and control system representation of the various excitation systems now available that can be used to define input data requirements for computer programs, and can provide a consistent format in which manufacturers can respond to requests for excitation system data to be used for system studies.
Journal ArticleDOI

Application of Underfrequency Relays for Automatic Load Shedding

TL;DR: In this article, the authors describe the factors involved in applying underfrequency relays to achieve a desired "deficient generation" protection level and a calculating method to achieve optimum relay settings.
Journal ArticleDOI

Dynamic load modeling in Taipower system stability studies

TL;DR: Based on the component approach, two kinds of dynamic load models, including a single-motor model and a two-motors model, have been developed for the stability studies of the Taiwan power system as discussed by the authors.
Related Papers (5)