scispace - formally typeset
Open AccessJournal ArticleDOI

Study on The Novel Transient Bus Protection Based on Morphological Top-bottom-operator

Hongchun Shu, +2 more
- 28 May 2011 - 
- Vol. 3, Iss: 3, pp 33-39
Reads0
Chats0
TLDR
A novel transient component bus protection based on mathematical morphology is presented in this paper, which takes the morphological max top-bottom- operator of current traveling wave to fast distinguish the bus internal fault from the external fault.
Abstract
A novel transient component bus protection based on mathematical morphology is presented in this paper, which takes the morphological max top-bottom- operator of current traveling wave to fast distinguish the bus internal fault from the external fault. The method is based on the principle that the high frequency component of transient traveling wave caused by bus external fault will be attenuated by the bus capacitance but the traveling wave caused by bus internal fault changes slightly. Simulation is carried out with the electromagnetic transient simulation software PSCAD/EMTDC, the result verifies the bus protection is reliable and accurate. The novel bus protection also can treat lightning failure or lightning disturbance happened on transmission lines as bus external fault, without malfunction.

read more

Content maybe subject to copyright    Report

Citations
More filters
Proceedings ArticleDOI

Six Phase Transmission Line Boundary Protection Using Mathematical Morphology

Gaurav Kapoor
TL;DR: The proposed method makes use of fault current samples rescued at the relay location for a variety of boundary faults at different operating conditions of a 400 kV, 50 Hz and 200 km long six phase power transmission line.
Journal ArticleDOI

Optimal instantaneous prediction of voltage instability due to transient faults in power networks taking into account the dynamic effect of generators

TL;DR: In this article , an index based on the changes of two indices of frequency deviation and frequency response of inertia is presented, which has the ability to detect the occurrence of instability and at the same time high speed timely estimation of voltage instability in the power system.
Journal ArticleDOI

Ultra-fast busbar protection employing fast S transform of current signals

TL;DR: According to the simulation results, the proposed algorithm has high security and dependability and very fast operation and it is immune to fault type, fault inception angle (FIA) and fault resistance.
Journal ArticleDOI

Fast transient-based detection of busbar faults employing improved morphological gradient

TL;DR: The proposed algorithm has high security and dependability in discrimination of external and internal faults with the ultra-fast operation and in the case of the existing two busbars in a substation layout, the proposed indices can discriminate between the faults of the two bus zones.
Proceedings ArticleDOI

Ultra-Fast Busbar Protection by Applying Improved ACUSUM

TL;DR: The proposed algorithm has high security and dependability in discrimination between external and internal faults and has a very fast operation and it is immune to fault type, fault inception angle and fault resistance.
References
More filters

Single-Ended Transient-based Protection for EHV Transmission Lines Basic Theory

TL;DR: In this article, the authors apply frequency domain model of transmission system to analyze the frequency characteristics of transmission line, busbar and line trap, and propose the concept of line boundary.

A distributed bus protection using transient traveling wave power directions of transmission lines

TL;DR: In this article, a distributed bus protection is proposed to distinguish internal and external faults of the protected bus by comparing the power directions of transient traveling-waves of transmission lines using the wavelet transform.

Effect of lightning on protection based on travelling waves

Dong Xing-li
TL;DR: In this paper, a lightning criterion using current component and wavelet transform is brought forward to distinguish whether fault takes place or not when lightning hits on transmission line, which can be fulfilled either by current itself or by fault component of current.

Study status and theories of protection for transmission lines based on travelling wave

TL;DR: In this paper, a background of the development of the travelling wave based relaying for transmission lines is introduced and its development at home and aboard is reviewed, and the advantages and disadvantages of various travelling wave-based relaying theories are analyzed.
Related Papers (5)