scispace - formally typeset
Open AccessDOI

A new monitor for pollution on power line insulators. Part 1: Design, construction and preliminary tests

S. E. D. Habib, +1 more
- Vol. 133, Iss: 2, pp 105-108
TLDR
In this paper, the leakage current drawn by an insulator chain of a power line in a polluted atmosphere is detected by a novel current transformer arrangement, whose amplitude exceeds a critical level, occurring over a preset period.
Abstract
Apparatus is developed for monitoring the leakage current drawn by an insulator chain of a power line in a polluted atmosphere. The apparatus senses the leakage current bursts by a novel current transformer arrangement. The apparatus counts the number of bursts, whose amplitude exceeds a critical level, occurring over a preset period. If this number reaches a critical value corresponding to a potentially dangerous intensity of the insulator pollution, the apparatus transmits an alarm signal to the service crew so that they would thus clean the power line insulators in time before a sudden line outage occurs, with the entailed excessive expense, loss of power supply and annoyance to customers. Line insulator cleaning is thus carried out only when necessary, which adds to the economy of the power system operation. The apparatus was designed, built and is currently being tested in the high voltage laboratory of Cairo University. Experience with it on actual power networks will be the subject of another paper.

read more

Citations
More filters
Journal ArticleDOI

Evaluation of feeder monitoring parameters for incipient fault detection using Laplace trend statistic

TL;DR: In this article, a systematic and cumulative statistical approach for identifying symptom parameters of incipient faults in distribution feeders is proposed, which aims at providing a tool for evaluating and identifying the best and highly correlated parameters to the faults so that they could be used for incipient fault detection and feeder condition monitoring.
Journal ArticleDOI

A study on the characterization of the incipient failure behavior of insulators in power distribution line

TL;DR: In this article, a feasibility study on the characterization of incipient insulator failure for distribution fault prediction is presented, where real distribution data was collected and analyzed to isolate incipient failure signatures or parameters which were expected to show distinct behaviors before and after failure incident.

Evaluation of Feeder Monitoring Parameters for Incipient Fault Detection Using

TL;DR: In this article, a systematic and cumulative statistical approach for identifying symptom parameters of incipient faults in distribution feeders is proposed, which aims at providing a tool for evaluating and identifying the best and highly correlated parameters to the faults so that they could be used for incipient fault detection and feeder condition monitoring.
Journal ArticleDOI

Relation between leakage impedance and equivalent salt deposit density on an insulator under a saltwater spray

TL;DR: In this paper, the authors measured the leakage current of an insulator under 30 V ac voltage and found that the leakage impedance does not depend on initial dryness of the insulator surface and the conductance is low.
Journal ArticleDOI

Experimental techniques to simulate naturally polluted high voltage transmission line insulators

TL;DR: In this article, experimental techniques to simulate the naturally polluted high voltage insulators, under conditions that simulate the desert environment are presented, where the surface of the insulator is polluted naturally over a relatively long period, while it is permanently under high voltage.
Related Papers (5)