TLDR
In this paper, the authors studied the relationship between the comprehensive information sensing data in the high-voltage distribution cabinet and the mechanical strength weakening of the cable joint, and established an early warning method of joint looseness.Abstract:
In view of the problem that the cable joint looseness or other mechanical abnormalities in the high-voltage distribution cabinet is difficult to predict in time, through this project, the corresponding relationship between the comprehensive information sensing data in the high-voltage distribution cabinet and the mechanical strength weakening of the cable joint is studied, and the early warning method of joint looseness is established to improve the operation reliability of the distribution cableIn order to deeply study the characteristics of loose electrical connection fault of bolted cable and realize effective fault identification, taking bolted cable joint as the research object, the loose fault test under different loose degree and different current conditions was carried out by using cable joint loosening fault test platform. Based on the principle of fuzzy structural element, according to the influence factors of current, power factor and vibration state of cable joint, the structural element expression of fuzzy comprehensive evaluation is given, and the loose fault of bolted cable joint is comprehensively evaluated. The results show that the method can effectively identify the loose state of bolted cable joint, and provide theoretical basis for detection and protection of loose fault.read more
References
More filters
Journal ArticleDOI
Multiobjective Battery Storage to Improve PV Integration in Residential Distribution Grids
TL;DR: In this article, a multiobjective optimization method is proposed to visualize the trade-offs between three objective functions: voltage regulation, peak power reduction, and annual cost, applied to a near future scenario, based on a real residential feeder.
Proceedings ArticleDOI
Electrical Contacts Condition Diagnostics Based on Wireless Temperature Monitoring of Energized Equipment
TL;DR: In this article, the authors present industrial case studies of continuous temperature monitoring of electrical contacts in energized equipment using wireless system with miniature temperature sensors and demonstrate its importance for properly and timely performed condition-based maintenance preventing possible disruption of electrical service.