scispace - formally typeset
Journal ArticleDOI

DGA comparison between ester and mineral oils

TLDR
In this paper, a comparative study between mineral and various ester oils based on Dissolved Gas Analysis (DGA) was performed at laboratory scale, then gas formation as well as diagnosis methods were compared.
Abstract
This paper reports on a comparative study between mineral and various ester oils based on Dissolved Gas Analysis (DGA). Electrical (breakdown of low energy) and thermal (stray gassing) faults were realized at laboratory scale, then gas formation as well as diagnosis methods were compared. Two extraction methods, described in IEC 60567 Ed.3 and independent from partition/solubility coefficients were used: multi-cycle vacuum degassing and stripping. Three different diagnosis methods were applied: IEC gas ratios, Duval's triangle and key gases. For electrical faults and especially for low energy discharges, the same main gases (Hydrogen and Acetylene) are created in relatively same ratios, thus confirming the efficiency of key gases method for ester oils. It is also shown that classic Duval's triangle (triangle 1) is well applicable for this type of fault confirming the results reported in literature. For thermal faults and especially for stray gassing issue (low thermal faults), Ethane (associated with Hydrogen) constitutes the key gas of natural esters. The new Duval?s triangles can be applied: Triangle 4 for mineral oil and Triangle 6 for ester oils. For extraction methods and in both electrical and thermal faults cases, it can be noted that results are comparable for mineral oil whereas they are slightly underestimated with stripping method for ester oils. The higher viscosity of ester could interfere with the extraction.

read more

Citations
More filters
Journal ArticleDOI

A critical review of plant-based insulating fluids for transformer: 30-year development

TL;DR: In this article, the research status of plant-based insulating fluids for transformer, including both challenges and outlook circa 2020, is reviewed, with a focus on the fire-safety and environmental requirements.
Journal ArticleDOI

Development of a new graphical technique for dissolved gas analysis in power transformers based on the five combustible gases

TL;DR: In this article, the authors proposed a novel graphical technique for DGA based on all the five combustible gases, which is developed in the form of a pentagon shape, where the pentagon heads represent the percentage concentration of each individual gas to the total combustible gas.
Journal ArticleDOI

Performance of coconut oil as an alternative transformer liquid insulation

TL;DR: In this paper, three different types of coconut oil samples consisting of virgin, copra and RBD (refined, bleached and deodorized) were initially tested by frequency dielectric spectroscopy (FDS) measurements to see how the conductivity was improved by dehydration and neutralization.
Journal ArticleDOI

Analysis of artificial intelligence expert systems for power transformer condition monitoring and diagnostics

TL;DR: In this article, an artificial intelligence-based methodology for power transformers fault detection and classification is presented, which can assist the operator's engineers in decision making about urgency of intervention and type of maintenance of power transformer.
Journal ArticleDOI

A Review on Synthetic Ester Liquids for Transformer Applications

TL;DR: In this paper, the authors present the recent research progress on synthetic ester liquid in relation to the selected issues, most important for ester development in the authors' opinion, including breakdown performance of synthetic esters, lightning impulse strength and pre-breakdown phenomena.
References
More filters
Book

IEEE guide for the interpretation of gases generated in oil-immersed transformers

TL;DR: In this paper, a detailed procedure for analyzing gas from gas spaces or gas-collecting devices as well as gas dissolved in oil is described, including the calibration and use of field instruments for detecting and estimating the amount of combustible gases present in gas blankets above oil, or in gas detector relays.
Journal ArticleDOI

The duval triangle for load tap changers, non-mineral oils and low temperature faults in transformers

TL;DR: New versions of the Duval triangle for equipment filled with mineral oil have been proposed for load tap changers of the oil type, equipmentfilled with non- mineral oils, and for low-temperature faults where stray gassing of oils may interfere with diagnostics as discussed by the authors.
Journal ArticleDOI

Experimental investigations on insulating liquids for power transformers: Mineral, ester, and silicone oils

TL;DR: In this article, the dielectric strength, electrostatic charging tendency (ECT), ageing stability, gassing tendency, heat transfer efficiency and stray gassing issue of mineral and silicone oils, synthetic and natural esters are analyzed and discussed.
Journal ArticleDOI

Dissolved gas analysis of alternative fluids for power transformers

TL;DR: In this paper, the authors proposed a new ratio criteria for fault detection and diagnosis of Ester-based transformer fluids with the same DGA fingerprints as mineral oil, but with lower volumes of gas produced.