scispace - formally typeset
Journal ArticleDOI

Terminal voltage regulation characteristics by static var compensator for a three-phase self-excited induction generator

TLDR
In this paper, a three-phase self-excited induction generator (SEIG) with squirrel-cage rotor is presented along with its operating performance evaluations for small-scale clean renewable and alternative energy utilizations.
Abstract
In this paper, the practical impedance approach steady-state analysis in the frequency domain for the three-phase self-excited induction generator (SEIG) with squirrel-cage rotor is presented along with its operating performance evaluations. The three-phase SEIG is driven by a variable-speed prime mover(VSPM) in addition to a constant-speed prime mover (CSPM) such as a wind turbine and a micro gas turbine for clean alternative renewable energy in rural areas. The basic steady-state characteristics of the VSPM are considered in the three-phase SEIG approximate equivalent circuit and the operating performance of the three-phase SEIG coupled with a VSPM and/or a CSPM are evaluated and discussed online under the conditions related to the speed changes of the prime mover and the electrical inductive load power variations with simple computation processing procedures. A three-phase SEIG prototype setup with a VSPM is implemented for small-scale clean renewable and alternative energy utilizations. The experimental performance results give good agreement with those obtained from the simulation results. Furthermore, a proportional-integral (PI) closed-loop feedback voltage regulation of the three-phase SEIG driven by the VSPM on the basis of the static var compensator (SVC) composed of the thyristor phase-controlled reactor in parallel with the thyristor switched capacitor and the fixed-excitation capacitor bank is designed and considered for the wind generation as a renewable power conditioner. The simulation analysis and experimental results obtained from the three-phase SEIG with SVC for its voltage regulation prove the practical effectiveness of the additional SVC with the PI-controller-based feedback loop in steady-state operation in terms of high performance with low cost.

read more

Citations
More filters
Journal ArticleDOI

Implementation of modified current synchronous detection method for voltage control of self-excited induction generator

TL;DR: In this article, a modified current synchronous detection method for voltage control of self-excited induction generator (SEIG)-based standalone power generating system using a static reactive power compensator (STATCOM) is presented.
Journal ArticleDOI

Dynamic Performances of Self-Excited Induction Generator Feeding Different Static Loads

TL;DR: In this article, the authors examined the dynamic performances of a three-phase self-excited induction generator (SEIG) during sudden connection of static loads and presented a dynamic flux model of the SEIG in the ˺-˻ axis stationary reference frame.
Journal ArticleDOI

Comparison of steady state characteristics of shunt, short-shunt and long-shunt induction generators

TL;DR: In this article, the authors present a comparative study of steady state characteristics of a self-excited induction generator operating in shunt, short-shunt and long-Shunt configurations.
Proceedings ArticleDOI

Voltage regulation of a stand-alone induction generator using thyristor-switched capacitors

TL;DR: In this article, a simple thyristor-switched capacitor (TSC) type voltage regulator was proposed for a stand-alone induction generator to maintain voltage within the upper and lower acceptable limits.
Journal ArticleDOI

Digital Signal Processor Based Fuzzy Voltage and Frequency Regulator for Self-excited Induction Generator

TL;DR: In this paper, a digital signal processor based fuzzy logic load controller is proposed to regulate the voltage and frequency of a three-phase self-excited induction generator through an equal time ratio control AC chopper controllable load that is suitable for a stand-alone power mode employing an unregulated turbine.
References
More filters

Static var compensator models for power flow and dynamic performance simulation

TL;DR: In this article, the static var compensator is now mature technology that is widely used for transmission applications and a standardization of basic models is recommended, and is recommended in this paper.
Journal ArticleDOI

The dynamic characteristics of an isolated self-excited induction generator driven by a wind turbine

TL;DR: In this article, the effect of magnetizing inductance on self-excitation was discussed and the loading analysis of an isolated induction generator, and how the operating frequency and generated voltage were affected by the change in operating slip value for regulated and unregulated rotor speed.
Journal ArticleDOI

Capacitance requirement for isolated self-excited induction generator

TL;DR: In this article, the authors derived the minimum capacitance required for self-excitation and the output frequencies under no-load, inductive and resistive loads, and showed that there is a speed threshold below which no excitation is possible no matter what the capacitance value.
Journal ArticleDOI

Static Exciters for Induction Generators

TL;DR: In this article, a simple exciter scheme based on using a static reactive power generator implemented with fixed capacitors and thyristor controlled inductors is proposed. But the feasibility of the proposed scheme with naturally commutated thyristors is verified by measurements on a test setup employing a standard 15-hp induction motor.
Journal ArticleDOI

Voltage-frequency control of a self-excited induction generator

TL;DR: In this article, a new strategy for controlling voltage and frequency of a self-excited induction generator (SEIG) is presented, which operates in the linear region of the core magnetizing curve, so that efficiency and performance are upgraded.
Related Papers (5)