Comparison of Impulse Wave and Sweep Frequency Response Analysis Methods for Diagnosis of Transformer Winding Faults

Qing Yang, +2 more
- 28 Mar 2017 - 
- Vol. 10, Iss: 4, pp 431
TLDR
In this paper, a tapped transformer is designed and test platforms are built to compare winding diagnoses using the impulse wave and sweep frequency response analysis methods by recording voltage responses on both the high and low-voltage sides and calculating the respective transfer functions.
Abstract
Monitoring of winding faults is the most important item used to determine the maintenance status of a transformer. Commonly used methods for winding-fault diagnosis require the transformer to exit operation before testing and an external exciting signal, whether the transformer is malfunctioning or not. However, if an overvoltage signal can be regarded as a broadband excitation source for fault diagnosis, then the interference caused by signal injection can be eliminated without the need for additional pulse or impulse signals. In this paper, a tapped transformer is designed and test platforms are built to compare winding diagnoses using the impulse wave and sweep frequency response analysis methods by recording voltage responses on both the high- and low-voltage sides and calculating the respective transfer functions. Based on comparison of statistical indicators, it is found that the sensitivities of both methods are similar for detecting conditions of winding-ground and winding-interlayer short circuits. It is concluded that it is feasible to use a transient overvoltage monitoring system for winding-fault diagnosis.

read more

Citations
More filters
Proceedings ArticleDOI

Application of the Impulse Response of Transformer Winding for Detection of Internal Turn-to-Turn Short Circuits

TL;DR: In this paper , the authors applied the impulse voltage method for the diagnosis of turn-to-turn short circuit faults inside a transformer winding, where the input signals are a set of impulse voltages of different shapes instead of the standard ac signals of variable frequency.
Proceedings ArticleDOI

An EHV Transformer Fault Diagnosis Method based on Acoustic Perception and Pseudo-Labels Intensive Training-CNN

TL;DR: In this paper , an EHV transformer fault diagnosis method based on acoustic perception and pseudo-labels intensive training-CNN is proposed in combination with semi-supervised training, and the final accuracy rate can reach more than 92.4 percent.
Proceedings ArticleDOI

An EHV Transformer Fault Diagnosis Method based on Acoustic Perception and Pseudo-Labels Intensive Training-CNN

TL;DR: In this paper , an EHV transformer fault diagnosis method based on acoustic perception and pseudo-labels intensive training-CNN is proposed in combination with semi-supervised training, and the final accuracy rate can reach more than 92.4 percent.

Online IFRA for Identification of Power Transformer Faults Based on Pulse Compression Method

TL;DR: In this article , the most accurate method, recommended for the energy transformers diagnostic, is the frequency response analysis (FRA), in the form of two implementations, Impulse-Frequency Response Analysis (IFRA), and Sweep-frequency Response analysis (SFRA), which have their own advantages, as well as difficulties when applied to a transformer without disconnecting them from the load.
References
More filters
Journal ArticleDOI

Transformer Diagnostic Testing by Frequuency Response Analysis

TL;DR: In this article, a frequency response analysis (FRA) method was used to measure wind deformation in power transformers, and the results indicated that benchmark reference data was not always necessary to identify certain kinds of mechanical damage.
Journal ArticleDOI

Monitoring of power transformers using the transfer function method

TL;DR: The transfer function concept is well known as an additional method of evaluating the impulse test of power transformers in the test laboratory and another application for this method is monitoring of power transformer in service as discussed by the authors.
Journal ArticleDOI

Decoupling the multiconductor transmission line equations

TL;DR: In this paper, a comprehensive discussion is presented of the method of decoupling the multiconductor transmission line (MTL) equations by transformation of the voltages and currents to mode voltages, in order to obtain their general solution.
Journal ArticleDOI

Passive multipoint moment matching model order reduction algorithm on multiport distributed interconnect networks

TL;DR: An integrated-congruence transform which can be directly applied to the partial differential equations of a distributed line and generate a passive finite order system as its model and an algorithm based on the L/sup 2/ Hilbert space theory so that exact moment matching at multiple points can be obtained.
Journal ArticleDOI

Diagnostic Measurements for Power Transformers

TL;DR: In this paper, the authors present the status and current trends of different diagnostic techniques of power transformers and provide significant tutorial elements, backed up by case studies, results and some analysis.
Related Papers (5)