scispace - formally typeset
Journal ArticleDOI

Consideration of skin effect in high-voltage coaxial systems under transient and steady-state conditions, and its impact on steep travelling waves

I.R. Jandrell, +1 more
- Vol. 138, Iss: 5, pp 445-451
Reads0
Chats0
TLDR
In this paper, the use of a ferromagnetic coating applied to the busbars of an SF6 busduct as a means of controlling disconnect transients is discussed and a software travelling wave model is described.
Abstract
The paper discusses the use of a ferromagnetic coating applied to the busbars of an SF6 busduct as a means of controlling disconnect transients. A software travelling wave model is described. The model is based on a frequency-domain characterisation of the busbars in the system. The model accounts for the skin effect in coated materials, and incorporates the effect of discontinuities in the system. The influence of the various coating attributes are noted. The model is shown to perform accurately as a travelling-wave analysis tool. Consideration is also given to the transient skin effect, which is shown to increase the attenuation of transients. Results recorded in a laboratory system with and without ferromagnetic busbars are presented. Ferromagnetics are shown to introduce marked risetime lengthening, as well as an envelope attentuation to disconnect transients.

read more

Citations
More filters
Journal ArticleDOI

New implementation of RSFQ superconductive digital gates

TL;DR: In this article, the NOR, NAND and XNOR gates were designed, simulated and laid out for fabrication in both IPHT's FLUXONICS 1 kA/cm 2 and Hypres' 4.5 kA /cm 2 processes.
References
More filters
Journal ArticleDOI

Time-domain skin-effect model for transient analysis of lossy transmission lines

TL;DR: A numerical method is used to analyze the transmission-line differential equations and the skin-effect equivalent circuit, yielding a model which relates the new values of node voltages and line currents to their values at the previous time step.
Journal ArticleDOI

Disconnect Switch Induced Transients and Trapped Charge in Gas-Insulated Substations

TL;DR: In this paper, field tests have been carried out which permitted direct measurement of disconnect switch operation induced transients in an operating 500 kV substation and the measurements indicate that transients do not exceed 2 pu at the point of measurement and that the trapped charge left on the load side is less than 0.3 pu.
Journal ArticleDOI

A Discussion on the Transient Analysis of Coaxial Cables Considering High-Frequency Losses

TL;DR: In this paper, a graphical transient analysis technique is described which allows one to easily analyze cables whose losses are due to a combination of physical processes and generalized curves based upon the (frequency) ^m approximation are presented by which the transient response of a cable can be rapidly evaluated for purposes of engineering design.
Journal ArticleDOI

Diffusion of Electric Current Into Rods, Tubes, and Flat Surfaces

TL;DR: In this article, the concept of thermal diffusion in transient heat flow is used to explain physically and evaluate numerically transient resistance and inductance of conductors subjected to rectangular current wave impulses.
Related Papers (5)