scispace - formally typeset
Journal ArticleDOI

Assessment of paper-oil insulation under copper corrosion using polarization and depolarization current measurements

TLDR
In this paper, the effect of temperature on polarization and depolarization current measurements on paper oil insulation system was discussed and the Debye model parameters of equivalent circuit under copper corrosion were computed and a model for failure due to copper sulphide was explained.
Abstract
This paper discusses the effect of temperature on polarization and depolarization current measurements on paper oil insulation system. The influence of copper sulphide formed due to corrosive sulphur in mineral oil, on the changes in polarization and depolarization current at different temperatures are considered. A significant increase in the magnitude of polarization and depolarization currents due to deposits of copper sulphide on paper layers is observed. The conductivity of paper insulation increases significantly with increase in temperature. The increase in current is attributed to thermally active conducting particles of copper sulphide. The Debye model parameters of equivalent circuit under copper corrosion have been computed and a model for failure due to copper sulphide is explained using the data on polarization and depolarization currents.

read more

Citations
More filters
Journal ArticleDOI

Factors affecting polarization and depolarization current measurements on insulation of transformers

TL;DR: Polarization and depolarization current measurements are promising on-site, off-line, non-destructive, noninvasive diagnostic tool for condition assessment of paper-oil insulation of transformers as mentioned in this paper.
Journal ArticleDOI

A New Method for Evaluating Moisture Content and Aging Degree of Transformer Oil-Paper Insulation Based on Frequency Domain Spectroscopy

TL;DR: In this article, a new method was proposed to evaluate the condition of oil-paper insulation based on compensation factors, thus distinguishing the internal influence between moisture content and aging degree on FDS.
Journal ArticleDOI

The microscopic morphology of insulation pressboard: an image processing perspective

TL;DR: In this article, the changes in microscopic morphology of the pressboard under surface partial discharge conditions, some methods such as enhancement, denoising, segmentation, optimization, edge detection, expansion, and corrosion were used to extract the fiber width, hole size, and surface roughness.
Journal ArticleDOI

Application of L1 Trend Filtering Technology on the Current Time Domain Spectroscopy of Dielectrics

TL;DR: In this paper, the authors applied L1 trend filtering to the current time domain spectroscopy of dielectrics and analyzed the robustness and time complexity of L 1 trend filtering.
Journal ArticleDOI

Polarization and Conduction Characteristics of Mineral Oil and Natural Ester Mixed with Nanoparticles

TL;DR: In this paper , the power frequency dielectric dissipation factor (tanδ) along with polarization and depolarization current (PDC) characteristics of the mineral oil-based nanofluid and natural ester (NE)-based nano-insulations were examined.
References
More filters
Journal ArticleDOI

Review of modern diagnostic techniques for assessing insulation condition in aged transformers

TL;DR: A description of commonly used chemical diagnostics techniques along with their interpretation schemes for transformer insulation condition assessment is presented.
Journal ArticleDOI

Applications of dielectric spectroscopy in time and frequency domain for HV power equipment

TL;DR: In this article, the authors proposed an off-line, on-site insulation condition assessment of HV electric power equipment and its predictive maintenance using dielectric spectroscopy in the time or frequency domain.
Journal ArticleDOI

Investigation of polarization and depolarization current measurements for the assessment of oil-paper insulation of aged transformers

TL;DR: In this article, the polarization and depolarization current (PDC) analysis is used for determining the conductivity and moisture content of insulation materials in a transformer, which is a non-destructive dielectric testing method.
Journal ArticleDOI

Deriving an equivalent circuit of transformers insulation for understanding the dielectric response measurements

TL;DR: In this article, a circuit model, which describes the dielectric behavior of the transformer's main insulation system, has been parameterized in order to identify the values of the parameters of the model and the correlation has been developed between the physical condition of the insulation and the equivalent model parameters that enable a clear and transparent interpretation of the test results.
Journal ArticleDOI

Investigations of Temperature Effects on the Dielectric Response Measurements of Transformer Oil-Paper Insulation System

TL;DR: In this paper, the effects of temperature on the dielectric measurements of a transformer under controlled laboratory conditions are investigated, and the results of practical on-site testing are also presented to demonstrate the possibility of errors that may be introduced in dielectrics test results analysis unless temperature effects are taken into consideration.
Related Papers (5)