scispace - formally typeset
Journal ArticleDOI

Active and reactive power control for doubly-fed wound rotor induction generator

M. Yamamoto, +1 more
- Vol. 6, Iss: 4, pp 624-629
Reads0
Chats0
TLDR
In this article, a power control system for a doubly fed wound rotor induction generator was developed, which applies a control method using a rotating reference frame fixed on the gap flux of the generator, and can control active and reactive power independently and stably.
Abstract
A power control system for a doubly fed wound rotor induction generator has been developed. This power control system applies a control method using a rotating reference frame fixed on the gap flux of the generator, and can control active and reactive power independently and stably. The characteristics of the control system have been proved by experiment. Harmonic currents fed to the rotor windings are transmitted to the stator winding changing its frequency. The transmitting characteristics of the harmonic currents have been analyzed and verified by experiments. >

read more

Citations
More filters
Journal ArticleDOI

Dynamic Modeling and Control of DFIG-Based Wind Turbines Under Unbalanced Network Conditions

TL;DR: In this article, a doubly-fed induction generator (DFIG)-based wind generation system operating under unbalanced network conditions is analyzed and control design of a DFIG system model in the positive and negative synchronous reference frames is presented.
Journal ArticleDOI

Overview of Control Systems for the Operation of DFIGs in Wind Energy Applications

TL;DR: The control systems for the operation of DFIGs in wind energy applications are reviewed for connections to balanced or unbalanced grids, and sensorless control.
Journal ArticleDOI

Control and performance of a doubly-fed induction machine intended for a flywheel energy storage system

TL;DR: In this article, the authors proposed a new control strategy for a doubly-fed induction machine intended as a flywheel energy storage system, which is characterized by the combination of vector control and decoupling control.
Journal ArticleDOI

Coordinated Control of DFIG's Rotor and Grid Side Converters During Network Unbalance

TL;DR: In this paper, a coordinated control of the rotor side converters (RSCs) and GSCs of doubly-fed induction generator (DFIG) based wind generation systems under unbalanced voltage conditions is illustrated.
Journal ArticleDOI

Small signal stability analysis and optimal control of a wind turbine with doubly fed induction generator

TL;DR: In this paper, a novel method using particle swarm optimisation (PSO) is proposed for optimising parameters of controllers of a wind turbine with doubly fed induction generator (DFIG).
References
More filters
Journal ArticleDOI

Cycloconvertor-excited divided-winding doubly-fed machine as a wind-power convertor

TL;DR: In this article, the authors describe a slip-ring induction machine operating as a doubly-fed generator above and below synchronous speed, where a prime mover simulates a wind turbine by producing a torque increasing in proportion to the square of the speed.
Journal ArticleDOI

Slip power recovery induction generators for large vertical axis wind turbines

TL;DR: In this article, the performance of a slip power recovery induction generator coupled to a vertical-axis wind turbine is discussed, and the suitability of this type of generator for wind-driven applications is discussed.
Journal ArticleDOI

Harmonics generated by two variable speed wind generating systems

TL;DR: In this article, two variable speed, constant frequency generating systems are tested on the MOD-0 experimental wind turbine to quantify the harmonic currents and voltages at the connecting point to the utility system.
Related Papers (5)