scispace - formally typeset
Journal ArticleDOI

Investigation and Improvement of Transient Response of DVR at Medium Voltage Level

TLDR
In this article, an effective and simple resonance damping method is proposed by employing a closed-loop control with an embedded two-step Posicast controller, which has been extensively tested on a 10-kV DVR system.
Abstract: 
An area of interest for dynamic voltage restorer (DVR) research is the damping of transient oscillations initiated at the start and at the recovery instant from a voltage sag. Nonlinear loads, with harmonic currents close to the DVR filter resonance frequency, can also excite the resonance oscillations. To compensate voltage sags and dampen high-frequency oscillations simultaneously, an investigation of the transient response of DVR is first carried out. Possible control schemes and their effects on the oscillation attenuation are also studied. Such studied control schemes include the commonly used single voltage loop control, voltage feedback plus reference feedforward control, and double-loop control with an outer voltage loop and an inner current loop. Subsequently, an effective and simple resonance damping method is proposed by employing a closed-loop control with an embedded two-step Posicast controller. The proposed control methods have been extensively tested on a 10-kV DVR system. It is shown that the proposed damping methods improve both the transient and steady-state performance of the DVR.

read more

Citations
More filters
Journal ArticleDOI

Effects of Discretization Methods on the Performance of Resonant Controllers

TL;DR: An exhaustive study about different discrete-time implementations of resonant controllers, extending to the discretization of the schemes with delay compensation, which is proved to be of great importance in relation with their performance.
Journal ArticleDOI

Control and Resonance Damping of Voltage-Source and Current-Source Converters With $LC$ Filters

TL;DR: To further dampen the LC resonance in these converter systems, active damping techniques such as virtual harmonic damper and control-signal-shaping methods are investigated, and their implementation into the converter systems is discussed in detail.
Journal ArticleDOI

A Modified Three-Phase Four-Wire UPQC Topology With Reduced DC-Link Voltage Rating

TL;DR: The proposed topology enables UPQC to have a reduced dc-link voltage without compromising its compensation capability, and helps to match the dc- link voltage requirement of the shunt and series active filters of the UpQC.
Journal ArticleDOI

Mitigation of Voltage Disturbances Using Dynamic Voltage Restorer Based on Direct Converters

TL;DR: In this paper, two new topologies are proposed for three-phase dynamic voltage restorers (DVRs) based on direct converters, which do not require dc-link energy storage elements.
Journal ArticleDOI

A comprehensive review of dynamic voltage restorers

TL;DR: In this article, the authors provide a comprehensive review on the DVR topologies, control strategies and applications, and some comparative conclusions are also provided for the researchers and engineers, who want to do investigations on DVRs.
References
More filters
Journal ArticleDOI

Stationary frame current regulation of PWM inverters with zero steady-state error

TL;DR: In this article, the P+Resonant regulator is proposed, which achieves the same transient and steady-state performance as a synchronous frame PI regulator and is applicable to both single-phase and three-phase inverters.
Proceedings ArticleDOI

Stationary frame current regulation of PWM inverters with zero steady state error

TL;DR: In this paper, a new type of stationary frame controller is proposed, which achieves the same steady state performance as a synchronous frame controller, and is applicable to both single phase and three phase inverters.
Journal ArticleDOI

Frequency domain analysis of three phase linear current regulators

TL;DR: In this article, a technique for interpreting the stationary/rotating frame transformations as modulation processes in the Laplace domain is presented, which moves the control function from one part of the frequency spectrum to another.
Journal ArticleDOI

Control and testing of a dynamic voltage restorer (DVR) at medium voltage level

TL;DR: In this paper, the effect of the dynamic voltage restorer (DVR) on a distribution test facility in Kyndby, Denmark is investigated under both faulted and non-faulted system states, for a variety of linear and nonlinear loads.
Journal ArticleDOI

Microgrid power quality enhancement using a three-phase four-wire grid-interfacing compensator

TL;DR: In this paper, a three-phase four-wire grid-interfacing power quality compensator for microgrid applications is proposed for use with each individual distributed generation (DG) system in the microgrid and consists of two four-phase-leg inverters (a shunt and a series), optimally controlled to achieve an enhancement of both the quality of power within the micro-grid and quality of currents flowing between the micro grid and the utility system.
Related Papers (5)