scispace - formally typeset
Open AccessJournal ArticleDOI

High-Frequency Power Transformers With Foil Windings: Maximum Interleaving and Optimal Design

Reads0
Chats0
TLDR
In this paper, the authors presented a novel interleaving technique, named maximum interleaved, that makes it possible to minimize the winding losses as well as the construction difficulty.
Abstract
Foil conductors and primary and secondary interleaving are normally used to minimize winding losses in high-frequency (HF) transformers used for high-current power applications. However, winding interleaving complicates the transformer assembly, since taps are required to connect the winding sections, and also complicates the transformer design, since it introduces a new tradeoff between minimizing losses and reducing the construction difficulty. This paper presents a novel interleaving technique, named maximum interleaving , that makes it possible to minimize the winding losses as well as the construction difficulty. An analytical design methodology is also proposed in order to obtain free-cooled transformers with a high efficiency, low volume, and, therefore, a high power density. For the purpose of evaluating the advantages of the proposed maximum interleaving technique, the methodology is applied to design a transformer positioned in the 5 kW–50 kHz intermediate HF resonant stage of a commercial PV inverter. The proposed design achieves a transformer power density of 28 W/cm3 with an efficiency of 99.8%. Finally, a prototype of the maximum-interleaved transformer is assembled and validated satisfactorily through experimental tests.

read more

Content maybe subject to copyright    Report

1
Abstract Foil conductors and primary and secondary
interleaving are normally used to minimize winding losses in
high-frequency transformers used for high-current power
applications. However, winding interleaving complicates the
transformer assembly, since taps are required to connect the
winding sections, and also complicates the transformer design,
since it introduces a new tradeoff between minimizing losses and
reducing the construction difficulty. This paper presents a novel
interleaving technique, named maximum interleaving, that makes
it possible to minimize the winding losses as well as the
construction difficulty. An analytical design methodology is also
proposed in order to obtain free-cooled transformers with a high
efficiency, low volume and, therefore, a high power density. For
the purpose of evaluating the advantages of the proposed
maximum interleaving technique, the methodology is applied to
design a transformer positioned in the 5 kW-50 kHz intermediate
high-frequency resonant stage of a commercial PV inverter. The
proposed design achieves a transformer power density of
28 W/cm
3
with an efficiency of 99.8%. Finally, a prototype of the
maximum-interleaved transformer is assembled and validated
satisfactorily through experimental tests.
Index Terms Foil windings, high-frequency, maximum
interleaving, optimization, transformer design.
I. INTRODUCTION
or applications requiring galvanic isolation, the line-
frequency transformer has traditionally been the
heaviest, most expensive and least efficient component part of
an electronic power converter. Nowadays, there is a large
number of medium power applications (1-25 kVA) with a
limited weight and space, such as electric traction systems,
distributed generation systems (PV panels and mini-wind
turbines) and power supplies, in which cost and efficiency are
paramount. In these applications, one of the most widely
adopted solutions for achieving considerable reductions in
weight and volume whilst significantly increasing efficiency,
yet still maintaining the required galvanic isolation, is to
Manuscript received September 15, 2014; accepted November 03, 2014.
Copyright © 2014 IEEE. Personal use of this material is permitted.
However, permission to use this material for any other purposes must be
obtained from the IEEE by sending a request to pubs-permission@ieee.org.
This work was supported in part by the Spanish Ministry of Economy and
Competitiveness under Grants DPI2010-21671-C02-01 and
DPI2013-42853-R and by the Public University of Navarre.
The authors are with the Department of Electrical and Electronic
Engineering, Public University of Navarre, Pamplona, Spain (e-mail:
ernesto.barrios@unavarra.es; andoni.urtasun@unavarra.es;
alfredo.ursua@unavarra.es; luisma@unavarra.es; pablo.sanchis@unavarra.es).
increase the transformer operating frequency to the range of
1-150 kHz [1][4].
In order to reduce winding loss, the primary and secondary
windings of high-frequency (HF) transformers are usually
sectioned and interleaved, and special wire geometries, such
as litz and foil conductors, are used [5][7]. Compared to litz
wire, a foil conductor is preferred due to its higher width-to-
thickness ratios, which provide lower DC resistances and
higher fill factors, its better heat conduction which facilitates
heat transfer to the environment, and its lower cost [1], [8].
However, the conventional procedure for interleaving foil
windings complicates the transformer assembly since taps are
required to connect in series the beginning and end of each
winding section. Although special techniques have been
proposed to interleave windings and minimize both losses and
assembly difficulty [8], [9], they have limitations since they
are only applicable either to transformers with turns ratios that
are close to the unity or to planar transformers.
Furthermore, the design of HF transformers needs to
address the interdependence between core sizing, foil
thickness sizing and winding interleaving, which complicates
the design process. The problem is usually solved by means of
an iterative process that depends on the designer's experience
and may entail the omission of some of the complex
electromagnetic, thermal and construction interdependencies
existing amongst the design parameters [5][7], [10][14].
To address the challenge of optimal HF transformer design,
this work proposes firstly an innovative technique, termed
maximum interleaving, which makes it possible to minimize
losses whilst minimizing the number of taps required and,
consequently, the construction difficulty. Then, a novel
non-iterative analytical methodology to optimally design HF
transformers is proposed, leading to the direct resolution of the
design problem as a non-linear optimization problem of only
four design variables. The methodology comprehensively
formulates the complex multi-physical phenomena present in
the operation of a HF transformer and the dependencies that
arise between these phenomena in the transformer design
process.
Moreover, given the fact that winding interleaving may not
be advisable in some applications, such as when a high
leakage inductance or a low interwinding capacitance is
required or in high voltage applications, the scope of the
design methodology proposed in this paper is extended to
High-Frequency Power Transformers with Foil
Windings: Maximum Interleaving and Optimal
Design
Ernesto L. Barrios, Student Member, IEEE, Andoni Urtasun, Student Member, IEEE, Alfredo Ursúa,
Member, IEEE, Luis Marroyo, Member, IEEE, and Pablo Sanchis, Senior Member, IEEE
F

2
include a non-interleaved approach. This is then used as a
reference point to assess the advantages of the maximum
interleaving technique.
The paper is organized as follows. Section II presents the
models for the calculation of the core loss, foil winding loss
and transformer thermal resistance for use in the design
process. Section III explains the maximum interleaving and the
winding loss calculation when this technique is applied.
Section IV discusses the transformer design problem and
proposes the optimal design methodology. With this
methodology two theoretical designs for a PV application are
obtained in Section V, one with maximum-interleaved and the
other with non-interleaved windings. When comparing both
designs, the maximum interleaving design achieves the best
performance in terms of power density and efficiency. A
prototype for the maximum interleaving design is then built in
Section VI, paying particular attention to the assembly process
and the use of low-cost standardized materials. The prototype
is finally validated by means of experimental tests with
satisfactory results.
II. T
RANSFORMER MODELING
A. Core Loss and Geometry
In the transformer design, the calculation of the core loss is
made in practice through empirical formula based on the
Steinmetz equation [15]. For typical HF power transformer
applications, in which the voltage applied is rectangular in
form, with or without zero voltage periods, the modified
Steinmetz equation (MSE) [16], the improved generalized
Steinmetz equation (iGSE) [17], and the improved iGSE
(i
2
GSE) [18] have been shown to be accurate core loss
empirical models [18][20]. Each model improves the
accuracy of the previous one but with an increasing
complexity. Thus, the MSE is generally used to calculate the
core loss in design processes due to its good trade-off between
accuracy and simplicity [12]. Its expression is [16]:
( )
( )
cTopeTopeT
y
p
x
eqmc
VcccBffCP +=
01
2
2
1
ττ
(1)
where f is the applied voltage waveform frequency, B
p
is the
magnetic induction amplitude, τ
ope
is the operating temperature
of the magnetic material, V
c
is the magnetic core volume, C
m
,
x, and y, and c
T2
, c
T1
and c
T0
are the losses and temperature
coefficients for the material, respectively, as provided by the
manufacturers in their datasheets, and f
eq
is the equivalent
frequency:
dt
dt
dB
B
f
T
eq
=
0
2
22
2
π
. (2)
Fig. 1 shows the geometry of the double U and double E
cores commonly used in power applications. Traditionally, the
core geometry is characterized by five characteristic
dimensions: mean length turn of a winding that completely
fills the window (MLT
c
), equivalent volume including the core
and windings (V
e
), effective cross-sectional area of the core
(A
c
), window area (A
w
), and core volume (V
c
). The latter three
dimensions only depend on the type of core whilst the first
two also depend on the place where the windings are wound.
Table I shows, for the two most common winding and core
types, the five characteristic dimensions based on the three
non-dimensional coefficients c
1
, c
2
, c
3
and the dimensional
factor a defined in Fig. 1. In the fourth column, the
characteristic dimensions are expressed based on the
characteristic coefficients mlt
c
, v
e
, a
c
, a
w
, v
c
and the
dimensional factor a in order to facilitate its use in the design
process.
(a) (b)
Fig. 1. Characteristic dimensions MLT
c
, A
c
, A
w
, and V
c
, dimensional factor
a and form coefficient c1, c2, and c3, for the main power cores: (a)
double U and (b) double E.
By applying these generic form expressions, the core loss
can be expressed as follows:
y
pc
BaKP
=
3
1
(3)
where coefficient K
1
is:
( )
01
2
21
TTTc
x
mmag
cc
cvf
CkK
+
=
ττ
(4)
where k
mag
is the ratio between the losses for a non-sinusoidal
magnetic induction and those for a sinusoidal one, and can be
expressed as a function of the length of the zero-voltage
period in rad, θ, as follows [19]:
. (5)
B. Foil Winding Losses
When operating at high frequencies, the amplitude and non-
uniformity of the current density distribution in the winding
cross-sectional area increases due to the well-known skin and
a
c1·a
A
w
A
c
V
c
MLT
c
c2·a
c3·a
a
c1·a
A
w
A
c
MLT
c
V
c
c2·a
c3·a
TABLE I . CHARACTERISTIC DIMENSIONS FOR MAIN POWER CORES:
DOUBLE E AND DOUBLE U
Core
characteristic
dimensions
Only one leg
double U
Shell type
double E
Generic
form
MLT
c
(2c1+c3+1)·a
2·(2c1+c3+1)·a
mlt·a
V
e
2·(c1+1)·(c2+2)
·(c3+c1a
3
2·(c1+1)·(c2+1)
·(c3+2·c1a
3
v
e
·a
3
A
c
c3·a
2
c3·a
2
a
c
·a
2
A
w
c1·c2·a
2
c1·c2·a
2
a
w
·a
2
V
c
2c3(c1+c2+2)a
3
2c3(c1+c2+5/4)a
3
v
c
·a
3

3
proximity effects. This can lead to an increase in winding loss.
In order to reduce this increase as far as possible foil
conductors are used. The calculation of the foil winding loss
has aroused great interest since Dowell’s work [21] and its
generalization in [22] until nowadays [23]. The power loss in a
foil winding section of p layers filling the full window height
with thickness h is calculated in this work by means of the
expression proposed by Snelling in [24] based on the
approximation of the analysis made by Dowell in [21] for
h δ:
+
=
4
2
2
45
15
1
δ
hp
I
RP
rmsdcw
(6)
where I
rms
is the rms winding current, δ is the skin depth, and
R
dc
is the dc resistance. The expressions for these latter two
parameters are:
µσπ
δ
=
i
f
1
, (7)
f
w
dc
wh
NMLT
R
=
σ
(8)
where f
i
is the current waveform frequency, MLT
w
is the mean
length turn of the winding, N is the number of turns, σ is the
material conductivity, μ is the magnetic permeability and w
f
is
the foil height. When the foil thickness is greater than the skin
depth, this expression overestimates the winding loss.
C. Thermal Modeling
It is possible to use both theoretical and empirical models to
estimate the thermal resistance of the transformer in a steady
state. A wide range of theoretical thermal models are
available, depending on the heat transfer mechanisms
considered and their interpretation. Empirical models achieve
a similar accuracy to theoretical ones, but with greater
simplicity [6], [11], and are therefore generally preferred for
use in the design process. In fact, the value of the transformer
thermal resistance R
th
is probably the most uncertain
parameter in the entire transformer design [13]. Studies made
by the magnetic material manufacturers show that it is
possible to establish an empirical relationship between the
thermal resistance of the transformer and the volume of its
core [25], [26]. Based on the data included by the
manufacturers in their application notes for various double E
and double U ferrite cores, for a temperature increase of 50 ºC,
and including the core volume in its generic form as shown in
Table I, the empirical formula for the thermal resistance R
th
of
a naturally-cooled transformer is as follows:
56.1
52.0
0457.0
av
R
c
th
=
(9)
where R
th
is expressed in ºC/W, v
c
is a non-dimensional factor
and a is expressed in meters. Very similar expressions are
commonly used in design processes for soft magnetic
materials with relatively high thermal conductivity such as
ferrites, nanocrystalline, and amorphous iron alloys [7].
III. M
AXIMUM INTERLEAVING: OPTIMAL WINDING
DISTRIBUTION
A. Conventional Interleaving
Thanks to the presence of a secondary winding, it is
possible to reduce the amplitude of the magnetomotive force
(f
mm
) in the window responsible for the proximity effect. With
this end, primary and secondary windings are usually divided
into sections and interleaved. The interleaving reduces the
number of layers per section p and, thus, as can be seen from
applying (6), also the losses in the interleaved winding.
However, this entails considerable construction difficulty as,
in order to series-connect the last turn of one section with the
start of the following section, taps need to be made. As a
result, the maximum feasible interleaving is limited by this
construction complexity [5], [8].
Considering now an example in which four turns for the
primary and eight for the secondary are required with primary
current value i, Fig. 2 shows three different possible winding
configurations and their resultant f
mm
distributions. As
indicated in Fig. 2 (a), one option is to make a 4-8 winding
arrangement, i.e. no interleaving, having a primary section
with four turns (p=4) and a secondary section with eight
(p=8). Consequently, maximum values are obtained for the f
mm
and proximity effect losses, and no taps are required, thereby
the winding process difficulty is minimum.
As shown in Fig. 2 (b), another option is to divide the
windings into two groups with a 2-4 configuration. This is an
intermediate interleaving comprising two primary sections
with two turns each (p=2) and two secondary sections with
four turns each (p=4). In this case, in comparison with the first
option above, the maximum f
mm
has been halved, leading to
lower losses. However, the construction process is more
complicated, consisting in making two turns with the insulated
primary foil and then cutting it. The insulated secondary foil is
then wrapped around the primary and cut. The process is then
repeated, but when starting the second primary section, the
end of the first section needs to be connected to the beginning
of this second section. This connection is called a tap. The
same procedure is followed for tapping the secondary sections.
This interleaving level is an acceptable trade-off between
losses and construction difficulty [5] and, therefore,
manufacturers do not usually continue increasing the
interleaving.
When the number of layers per section for the primary and
secondary is minimized, the windings are fully interleaved and
the f
mm
and the proximity effect losses are also minimized.
However, this design creates the greatest construction
difficulty, requiring the higher number of cuts and taps. As
indicated in Fig. 2 (c), in the example studied, the windings
are fully interleaved when four groups are formed with a 1-2
configuration. Consequently, six taps are needed; three taps to
series-connect the primary turns and another three to
series-connect the end of each secondary section with the
beginning of the next.

4
(a) (b) (c)
Fig. 2. Magnetomotive force in the cross section of a transformer window
for three different winding interleaving arrangements: (a) non-interleaved,
(b) intermediate interleaving, and (c) fully interleaved.
It should be pointed out that the interleaving affects the
parasitic elements of the transformer. The greater the
interleaving, the lower the energy stored in the stray magnetic
field and the greater the energy stored in the stray electric field
between the primary and secondary windings. In this way, the
greater the interleaving, the lower the leakage inductance and
the greater the capacity between the primary and secondary
windings [7]. Consequently, depending on the application, the
interleaving may not be advisable. For instance, when
electromagnetic interference (EMI) needs to be minimized,
when leakage inductance is used as a filter or resonant
components [27], [28], or in high voltage applications in
which primary and secondary windings are grouped into
separate chambers due to isolation concern, a non-interleaved
structure is preferred.
B. Maximum Interleaving of Foil Windings
In order to maximize the reduction of the proximity effect
yet without a complicated assembly, a new winding
interleaving technique, named maximum interleaving, is
proposed in this paper. With this technique, the f
mm
distribution is the same as for the conventional fully-
interleaved winding configuration, however, due to the
construction process proposed, the number of taps required is
reduced to the minimum technically necessary. In order to
make it easier to understand the proposed technique, this is
firstly applied to the example above (see Fig. 3) and it is then
generically described.
In the first step, three insulated foils are wound around the
magnetic core’s central leg to make four turns. The first foil
has the primary winding thickness, while the second and third
foils have the secondary thickness. Finally, and as detailed in
Fig. 3, the beginning of the third foil is soldered to the end of
the second foil through a tap, so that the second and third foils
are series connected and eight turns for the secondary winding
are completed. In so doing, the same minimum losses as for
conventional full interleaving are achieved yet with a much
simpler construction, given the fact that only one tap is needed
instead of the conventional six.
The maximum interleaving technique proposed in this paper
is generically described below. It can be easily applied to any
transformer ratio, even a non-integer number. The winding
with the least number of turns (N
A
) is termed A whilst the one
with the greatest number of turns (N
B
) is named B. One foil
conductor is taken for winding A, and p foil conductors for
winding B, with p equal to:
(a) (b)
Fig. 3. Maximum winding interleaving of a 4 primary and 8 secondary
turns foil transformer: (a) cross section of the magnetic core central leg,
and (b) window cross section (Section A-A’).
=
=
A
B
N
N
round
n
round
p
1
(10)
where generic transformation ratio n, taken as the quotient
between the number of turns for windings A and B, equal to
N
p
/N
s
for step-up transformers and N
s
/N
p
for step-down
transformers. The conductor for winding A and the p
conductors for B are insulated from each other and then placed
one on top of the other in order to proceed with the winding.
From here onwards, two cases can be differentiated:
- Decimal part of 1/n 0.5: Fig 4 shows the cross section of
the central leg of a double E core with a generic winding
distribution for this case. As can be seen, the conductors are
wound jointly and continuously, with the conductor of the
winding with the least number of turns positioned inside,
until z number of turns has been reached:
=
p
N
floorz
B
. (11)
Fig. 4. Cross section of a double E core with maximum interleaving when
1/n is rounded upwards. Winding A in blue and B in green.
Turn z indicates the end of the winding of the p-p’ external
conductors of winding B, where p’ is:
zN
pzN
p
A
B
='
. (12)
1׀1 5 ׀ 2 ׀ 2 6 ׀
3׀ 3 7 ׀4׀ 4 8
TAP
A
Section A-A’
A’
i
2i
3i
4i
0
x
f
mm
MAGNETIC CORE
i
2i
0
x
i
0
x
f
mm
f
mm
1 2 3 4 ׀ 1 2 3 4 5 6 7 8
1 2 ׀
1 2 3 4
׀ 3 4
׀ 5 6 7 8
1׀1 2 ׀ 2 ׀ 3
4 ׀
3׀ 5 6 ׀ 4׀
7 8
TAPS
1
1
p
p
p’
..
..
..
N
A
..
p’+1
p’
1
1
z
2
1
..
..

5
In this way, p-p’ foils of winding B are cut at turn z as
indicated by an x in Fig. 4. Then, the remaining turns are
wound until N
A
is reached, however in this case p’
conductors are used for winding B. Once the winding has
been completed, the next step is to use taps to connect in
series the ends of the various layers of the winding B. The
end of layer 1 is connected to the start of layer 2, and so on,
until the end of layer p-1 is connected to the start of layer p.
If p’ is less than 1, then this means that when z turns have
been wound, less turns need to be given to winding B than
to winding A. In these cases, it is sufficient to equal p’ to 1
and make the remaining turns until N
B
has been reached.
Then, the remaining turns are made for winding A until
reaching N
A
. An example of this special case is shown in
Section VI.
- Decimal part of 1/n 0.5: Fig 5 shows the cross section of
the central leg of a double E core with a generic winding
distribution for this case. Likewise, the windings are made
jointly and continuously, however locating the p conductors
of the winding with the largest number of turns on the
inside. So N
A
turns are made around the central leg of the
core, and then the winding of B is completed by one more
turn with p’ conductors:
pNNp
A
B
='
. (13)
For this purpose, the p-p’ external conductors of winding B
are cut and ended after turn N
A
. Finally, the layers of
winding B must be series connected. As in the case above,
the end of layer 1 must be connected to the start of 2 and so
on until the end of layer p-1 has been connected to the
beginning of layer p.
If p’ is greater than p, then after turn N
A
an additional turn
should be given with p conductors of winding B, cutting the
2p-p’ external conductors and giving an additional turn with
the remaining p’-p conductors.
Fig. 5. Cross section of a double E core with maximum interleaving when
1/n is rounded downwards.
It can be concluded that the maximum interleaving serves to
minimize the proximity losses in the transformer windings
whilst it also minimizes the construction complexity, given the
fact that the number of taps required is reduced to p-1.
C. Total Winding Losses Calculation
1) Maximum-Interleaved Windings
The expression for the total power loss in the transformer
windings when implementing maximum interleaving is now
obtained for use in the novel transformer design process
that is proposed in Section IV. Firstly, the number of turns
N for any winding can be expressed according to the
magnetic induction amplitude B
p
with frequency f by means
of the rms voltage equation V
rms
induced in the said
winding:
2
4 aa
B
fk
V
N
c
psh
rms
=
(14)
where k
sh
is the waveform factor, equal to 1 when a square
voltage is applied and to 1.11 when the voltage is
sinusoidal. For other voltage waveforms, k
sh
have to be
specifically calculated as indicated in [7].
When the maximum interleaving is implemented, it can
be assumed that the mean length turn MLT
w
is equal for
both transformer windings, and equal to the mean length of
the core MLT
c
. The winding with a least number of turns,
named A, has a single layer of thickness h
A
in all its
sections, whilst the other, named B, has p layers of
thickness h
B
in most of its sections and p’ in the rest. To
simplify the design process it is considered that, across the
length of the winding, there is a constant number of layers
per section p. Introducing (14) in (6), including the generic
expression for the characteristic core dimensions developed
in Table I, expressing the foil height w
f
as the height of the
window c2·a multiplied by height fill factor k
h
, and
particularizing for each of the windings, the losses are
obtained for the winding with the least number of turns P
wA
and for the winding with the greatest number of turns P
wB
:
+
=
4
3
2
,
2
,
45
4
1
2
4
δσ
A
A
p
ch
sh
rms
ArmsA
wA
h
h
a
Ba
ck
fk
VImlt
P
, (15)
( )
+
=
4
32
2
,
2
,
45
15
1
24
δσ
B
B
pchsh
rmsBrmsB
wB
hp
h
aBackfk
VImlt
P
.(16)
By referring voltages and currents to the winding with the
least number of turns by means of transformation ratio n
defined in (10), introducing δ according to the current
frequency f
i
in (7), and adding both expressions, the total
losses in transformer windings P
w,t
are obtained:
( )
[ ]
+++
=
323
3
2
2,
1
54
1
BA
BA
p
tw
hp
nhK
h
n
h
a
B
mlt
KP
(17)
where coefficients K
2
and K
3
have the following
expressions:
fackk
IV
K
chsh
rmsA
rmsA
=
2
4
2
,,
2
σ
, (18)
45
2222
3
i
f
K
=
σµπ
. (19)
..
1
p
1
..
1
p’
1
1
2
N
A
N
A
+1
p’
p
p’+1
..
..

Citations
More filters

Power electronics

Journal ArticleDOI

Optimal Design and Implementation of High-Voltage High-Power Silicon Steel Core Medium-Frequency Transformer

TL;DR: The detailed design considerations and an optimal design method are presented, and the test results show performance better than expected, with desirable no-load loss and power density of 2.9623 × 106 W/m3.
Journal ArticleDOI

Design and Implementation of an 18-kW 500-kHz 98.8% Efficiency High-Density Battery Charger With Partial Power Processing

TL;DR: In this article , an overall design procedure for a bidirectional soft-switching resonant-type partial power (PP) converter is proposed to solve the problem of tight coupling between two dc transformers (DCXs).
Journal ArticleDOI

Parasitic Capacitance Modeling of Copper-Foiled Medium-Voltage Filter Inductors Considering Fringe Electrical Field

TL;DR: In this article, a physics-based analytical modeling method for the parasitic capacitances contributed by the fringe electrical field is proposed, which avoids using any empirical equations and shows a close agreement with the measured capacitance by using an impedance analyzer.
Journal ArticleDOI

Semi-Empirical Model for Precise Analysis of Copper Losses in High-Frequency Transformers

TL;DR: This paper gathers intensive 2-D finite-element method (FEM) simulations into a base formula by means of a multivariable regression process to establish a novel semiempirical formula with five determinant geometrical parameters that is suitable for the majority of practical applications.
References
More filters
Book

Power Electronics

Rashid

Power electronics

Journal ArticleDOI

Effects of eddy currents in transformer windings

P.L. Dowell
TL;DR: In this article, the effect of eddy currents on transformer windings is considered and a method is derived for calculating the variation of winding resistance and leakage inductance with frequency for transformers with single-layer, multilayer and sectionalised windings.
Book

Transformer and inductor design handbook

TL;DR: In this paper, the authors present a theoretical analysis of transformer-inductor design, including the following: AC Inductor Design Powder Core. DC Inductor design Gap Core. Forward Converter Transformer and Inductor Development.
Proceedings ArticleDOI

Accurate prediction of ferrite core loss with nonsinusoidal waveforms using only Steinmetz parameters

TL;DR: An improved calculation of ferrite core loss for nonsinusoidal waveforms separates a flux trajectory into major and minor loops via a new recursive algorithm that is highly accurate and outperforms two previous methods for measured data.
Related Papers (5)
Frequently Asked Questions (1)
Q1. What are the contributions in this paper?

However, winding interleaving complicates the transformer assembly, since taps are required to connect the winding sections, and also complicates the transformer design, since it introduces a new tradeoff between minimizing losses and reducing the construction difficulty. This paper presents a novel interleaving technique, named maximum interleaving, that makes it possible to minimize the winding losses as well as the construction difficulty.