Considerations of a shunt active filter based on voltage detection for installation on a long distribution feeder
Keiji Wada,Hideaki Fujita,Hirofumi Akagi +2 more
- Vol. 38, Iss: 4, pp 1123-1130
Reads0
Chats0
TLDR
In this article, a distributed-parameter representation is applied to a simplified feeder, thus making it possible to perform analysis of the whack-a-mole phenomenon in a long distance distribution feeder having many capacitors for power-factor correction.Abstract:
This paper deals with a curious phenomenon referred to as the "whack-a-mole" that may occur in a long-distance distribution feeder having many capacitors for power-factor correction. The idea of whack-a-mole is that installation of an active or passive filter on the feeder makes voltage harmonics increase on some buses, whereas it makes voltage harmonics decrease on other buses, especially at the point of installation. The distributed-parameter representation is applied to a simplified feeder, thus making it possible to perform analysis of the whack-a-mole. As a result, this analysis yields such a basic way as to avoid the whack-a-mole. Moreover, both theory and experiment clarify that installation of the active filter acting as a harmonic terminator on the end bus of the feeder can damp out harmonic propagation throughout the feeder without causing any whack-a-mole.read more
Citations
More filters
Journal ArticleDOI
Advanced Control Architectures for Intelligent Microgrids—Part I: Decentralized and Hierarchical Control
TL;DR: Decentralized, distributed, and hierarchical control of grid-connected and islanded microgrids that mimic the behavior of the mains grid is reviewed.
Journal ArticleDOI
Active Harmonic Filters
TL;DR: This paper deals with general pure active filters for power conditioning, and specific hybridactive filters for harmonic filtering of three-phase diode rectifiers.
Journal ArticleDOI
Advanced Control Architectures for Intelligent Microgrids—Part II: Power Quality, Energy Storage, and AC/DC Microgrids
TL;DR: The use of static synchronous compensator in grid-connected microgrids is introduced in order to improve voltage sags/swells and unbalances and the coordinated control of distributed storage systems and ac/dc hybrid micro grids is explained.
Journal ArticleDOI
Secondary Control for Voltage Quality Enhancement in Microgrids
TL;DR: A hierarchical control scheme is proposed for enhancement of sensitive load bus (SLB) voltage quality in microgrids to manage the compensation of SLB voltage unbalance and harmonics by sending proper control signals to the primary level.
Journal ArticleDOI
Damping Methods for Resonances Caused by LCL-Filter-Based Current-Controlled Grid-Tied Power Inverters: An Overview
TL;DR: A comprehensive overview on the contributions and their classification on the inverter- and grid-side damping measures are presented and some promising damping methods for industrial applications will be discussed.
References
More filters
Journal ArticleDOI
New trends in active filters for power conditioning
TL;DR: In this article, the authors present the present status of active filters based on state-of-the-art power electronics technology, and their future prospects and directions toward the 21st Century, including the personal views and expectations of the author.
Journal ArticleDOI
Control Strategy and Site Selection of a Shunt Active Filter for Damping of Harmonic Propagation in Power Distribution Systems
TL;DR: In this article, a shunt active filter based on detection of voltage at the point of installation is compared to others, and the best site selection is not the beginning terminal but the end terminal of the primary line in the feeder.
Journal ArticleDOI
A shunt active filter based on voltage detection for harmonic termination of a radial power distribution line
TL;DR: In this paper, a shunt active filter based on the detection of harmonic voltages at the point of installation is proposed to attenuate harmonic propagation resulting from series/parallel resonance between capacitors for power factor correction and line inductors.
Journal ArticleDOI
Harmonic resonance at a medium sized industrial plant
TL;DR: In this paper, the authors used a harmonic analyzer at several locations in an electrical distribution system to quantify harmonic currents and voltages and found that harmonic resonance occurs near the seventh harmonic frequency depending on configuration of the electrical power system.
Proceedings ArticleDOI
Harmonic measurements, analysis, and power factor correction in a modern steel manufacturing facility
TL;DR: In this article, the analytical technique used to correct power factor in a modern steel manufacturing facility is presented, which included field measurements, harmonic analysis, and filter design work to reduce the amount of harmonic distortion in the plant.