scispace - formally typeset
Journal ArticleDOI

Micro-grid autonomous operation during and subsequent to islanding process

Reads0
Chats0
TLDR
In this paper, the authors investigated preplanned switching events and fault events that lead to islanding of a distribution subsystem and formation of a micro-grid, and they concluded that an appropriate control strategy for the power electronically interfaced DG unit can ensure stability of the microgrid and maintain voltage quality at designated buses, even during islanding transients.
Abstract
This paper investigates (i) preplanned switching events and (ii) fault events that lead to islanding of a distribution subsystem and formation of a micro-grid. The micro-grid includes two distributed generation (DG) units. One unit is a conventional rotating synchronous machine and the other is interfaced through a power electronic converter. The interface converter of the latter unit is equipped with independent real and reactive power control to minimize islanding transients and maintain both angle stability and voltage quality within the micro-grid. The studies are performed based on a digital computer simulation approach using the PSCAD/EMTDC software package. The studies show that an appropriate control strategy for the power electronically interfaced DG unit can ensure stability of the micro-grid and maintain voltage quality at designated buses, even during islanding transients. This paper concludes that presence of an electronically-interfaced DG unit makes the concept of micro-grid a technically viable option for further investigations.

read more

Citations
More filters
Journal ArticleDOI

Highlighting the Importance of Chronology on Voltage Protection and Control in Active Distribution Networks

TL;DR: In this article, the authors highlight the importance of chronology on voltage protection and control apparatuses in studies of voltage security in active distribution networks with high generation capacity and present simulation results of a real-life example of a long rural distribution feeder having three voltage regulators in cascade, and a customer whose demand accounts for a large percentage of the total feeder load.
Proceedings ArticleDOI

Research of automatic bus transfer in substation with DG connected

TL;DR: It is shown that scheme two can improve the reliability of automatic bus transfer and has better engineering value than scheme one, which was shown earlier.
Proceedings ArticleDOI

On load shedding in microgrids

TL;DR: In this paper, a MPPT algorithm is used to extract maximum power from PV sources and a controller is designed to stabilize MG performance during islanding, which can be used to prevent blackout of isolated system.
Proceedings ArticleDOI

Analysis on IIDG's negative-sequence current upon asymmetric fault

TL;DR: In this article, the negative-sequence current protection can be used in the distribution network containing inverter interfaced DG (IIDG), and the authors propose the protection principle for IIDG-containing distribution network.

Design of an Electronically-Interfaced Dispatchable Power Generation Source to Facilitate Islanding and Autonomous Operation of a Distribution Network

Farid Katiraei, +1 more
TL;DR: In this article, the authors proposed a distributed energy resource (DER) for the planned islanding and autonomous operation of a medium voltage distribution system with high-penetration of renewable energy resources, which is composed of a slow-response primary source and a short-term energy storage.
References
More filters
Book

Electrical Power Systems Quality

TL;DR: In this paper, the authors present a power quality evaluation procedure for the purpose of measuring the power quality of a power supply. But, they do not define the specific classes of power quality problems.

Vector analysis and control of advanced static VAr compensators

TL;DR: The advanced static VAr compensator (ASVC) as mentioned in this paper is based on the principle that a self-commutating static inverter can be connected between three-phase AC power lines and an energy storage device, such as an inductor or capacitor, and controlled to draw mainly reactive current from the lines.
Journal ArticleDOI

Vector analysis and control of advanced static VAr compensators

TL;DR: In this paper, two fundamentally different types of invertor can be used for this purpose, one providing control of output voltage magnitude and phase angle, and the other having only phase angle control.
Journal ArticleDOI

Protection against loss of utility grid supply for a dispersed storage and generation unit

TL;DR: In this paper, the requirements of an islanding, or "loss of grid", protection for a dispersed storage and generation unit are examined, and the principal methods used for this type of relaying are outlined.
Proceedings ArticleDOI

Distributed energy sources: technical challenges

TL;DR: In this article, the main related technical issues are discussed together with the DGs modelling requirements for their analysis, and the main technical issues of the micro-grid are discussed and discussed in detail.
Related Papers (5)